Overheat Analysis on the Connection Gap in GIS with the Sections Connected by Bolts

被引:0
|
作者
Ning Y. [1 ]
Sun H. [2 ]
Zhang W. [3 ]
Lu B. [2 ]
Ge D. [4 ]
机构
[1] Guangzhou Power Supply Bureau, Guangzhou
[2] Beijing Key Laboratory of High Voltage & EMC, North China Electric Power University, Beijing
[3] State Grid Hunan Maitainance Company, Changsha
[4] Maintenance Branch Company, State Grid Beijing Electric Power Corporation, Beijing
来源
Diangong Jishu Xuebao/Transactions of China Electrotechnical Society | 2017年 / 32卷
关键词
Bolt; Busbar; Gap; Gas insulated substation; Temperature field;
D O I
10.19595/j.cnki.1000-6753.tces.161561
中图分类号
学科分类号
摘要
The high-voltage busbar within GIS is usually segmented and assembled with steel bolt on site for ease of installation, transportation and maintenance. Gap may exist between some segmented busbars due to the tolerance, and in which only the steel bolts play the role of current conduction. Therefore when current is larger, the bolt can be melt gradually and fault may be occurred. In response to the short faults in some 220kV GIS, we investi-gated the temperature field distribution between the high-voltage busbars as well as its relationship with the current under different conditions. Furthermore, the coupled multi-physics model considered current, the connection gaps, bolts' material, thread geometries, heat-transfer coefficients and alumina membranes was also built based on the finite element method. The allowable maximal value of the current in three-phase and single-phase busbar in different situations was also calculated. The analysis indicates that the size of the gap has great influence on the temperature. And we find that the temperature will increase at around 10K to 50K with the gap when the bolt material is made of steel. This research will play a guiding role for GIS design and support theoretical base to ensure its long-term safety and reliable operation. © 2017, The editorial office of Transaction of China Electrotechnical Society. All right reserved.
引用
收藏
页码:217 / 234
页数:17
相关论文
共 23 条
  • [11] Castel G.S.P., Contact charging between metals revisited, IEEE Transactions on Industry Applications, 40, 5, pp. 1226-1230, (2004)
  • [12] Holm R., Electric Contacts: Theory and Application, (1967)
  • [13] Capp P.O., Williams D.W.M., Evaluation of friction and wear of new palladium alloy inlays and other electrical contact surfaces, Proceedings of International Conference on Electric Contacts Phenomena and 30th Annual Holm Conference on Electrical Contacts, pp. 410-416, (1984)
  • [14] Bejan A., Kraus A.D., Heat Transfer Handbook, (2003)
  • [15] Wu X., Shu N., Li H., Et al., Thermal field calculation and analysis of gas insulated busbars based on fluid multiple species transport, Proceedings of the CSEE, 32, 33, (2012)
  • [16] Sun G., Shu N., Wu X., Et al., Finite element analysis of contact temperature rise in gas insulated busbars based on coupled multi-physics, Transactions of China Electrotechnical Society, 28, pp. 408-413, (2013)
  • [17] Sun G., Guan X., Jin X., Et al., Temperature rise calculation and overheating fault analysis of gas insulated switchgear bus connector based on coupled field theory, High Voltage Engineering, 40, 11, pp. 3445-3451, (2014)
  • [18] Zhou L., Lu T., Luo R., Et al., Detection and evaluation method of electrical contact state in gas insulated switchgear, High Voltage Engineering, 41, 1, pp. 217-224, (2015)
  • [19] Fu Y., Wang Z., Wang N., Simulation and experiment investigation on a dual-electrode DC arc furnace with high smelting efficiency for MgO production, Transactions of China Electrotechnical Society, 31, 24, pp. 79-87, (2016)
  • [20] Jiang Z., Zhou H., Song J., Et al., Temperature field calculation and experimental analysis of dry-type air-core reactor, Transactions of China Electrotechnical Society, 32, 3, pp. 218-224, (2017)