Prediction of evaporation temperature in air-water heat source heat pump based on artificial neural network

被引:0
|
作者
Li, Chuanming [1 ]
Li, Nianping [1 ]
Tan, Xin [2 ]
Yongga, A. [1 ]
Long, Jibo [2 ]
Shen, Xiaohang [3 ]
机构
[1] Hunan Univ, Coll Civil Engn, Changsha 410082, Peoples R China
[2] Xiangtan Univ, Coll Civil Engn, Xiangtan City 411105, Peoples R China
[3] Hunan Inst Engn, Coll Architectural Engn, Xiangtan 411104, Hunan, Peoples R China
来源
关键词
Artificial neural network modeling; Air-water heat source heat pump; Finned evaporator; Evaporating temperature; Temperature prediction; ANN; OPTIMIZATION; PERFORMANCE; SYSTEM; MODEL; INTELLIGENCE; REGRESSION; EXCHANGER;
D O I
10.1016/j.jobe.2024.111036
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
To improve the low-temperature heating stability and performance of the air-source heat pump (ASHP), a heat transfer model was established for an air-water heat source heat pump (A-WSHP) in this study. Key factors affecting A-WSHP evaporating temperature were analyzed through simulation. An artificial neural network (ANN) prediction model for refrigerant evaporating temperature was developed using fin pitch, air velocity, air temperature, spray flow rate, spray water temperature, and droplet diameter as inputs. In the winter climate of Xiangtan City, this model predicts the refrigerant evaporating temperature and regulates it by adjusting various input parameters. Results indicate that fin pitch and droplet size significantly impact the refrigerant evaporating temperature, more so than fin thickness. The air temperature (34.78 %) and spray water temperature (38.02 %) have the highest weights, while fin thickness has the least influence, with a weight of 0.75 %. The R2 value of the ANN refrigerant evaporating temperature prediction model is 0.974, indicating a good fit. By properly adjusting the heat pump fan and spray valve, changes in air velocity and spray flow rate can enhance the refrigerant evaporating temperature, leading to stable and efficient heat pump operation. This research not only provides a theoretical basis for the operational strategy of air-water heat pumps but also offers guidance for frost-free operation in low-temperature environments.
引用
收藏
页数:19
相关论文
共 50 条
  • [21] Room Temperature Controlled Air-water Heat Pump with Free Air Intake from the Stove Room.
    Mueller, Roland
    Elektrowarme international. Edition A, Elektrowarme im technischen Ausbau, 1980, 38 (06): : 363 - 365
  • [22] Heat pump digital twin: An accurate neural network model for heat pump behaviour prediction
    Evens, Maarten
    Arteconi, Alessia
    APPLIED ENERGY, 2025, 378
  • [23] Performance prediction of heat exchangers based on model and artificial neural network
    Ding, GL
    Zhang, CL
    CRYOGENICS AND REFRIGERATION - PROCEEDINGS OF ICCR'2003, 2003, : 536 - 539
  • [24] Assessment of exergy efficiency and Sustainability Index of an air-water heat pump
    Dincer, I.
    Naterer, G. F.
    INTERNATIONAL JOURNAL OF EXERGY, 2010, 7 (01) : 37 - 50
  • [25] Prediction of Explosion Heat of Aluminized Explosive Based on Artificial Neural Network
    Tian, Xin
    Liu, Yonggang
    Jiang, Yueqiang
    PROCEEDINGS OF THE 2015 INTERNATIONAL CONFERENCE ON ELECTRICAL, ELECTRONICS AND MECHATRONICS, 2016, 34 : 80 - 82
  • [26] Defrosting characteristics and energy consumption of new air-water dual source composite heat pump system
    Xu J.
    Zhao Y.
    Quan Z.
    Wang H.
    Zhao H.
    Wang J.
    Zhao, Yaohua (yhzhao29@126.com), 2018, Materials China (69): : 2646 - 2654
  • [27] The use of artificial neural networks (ANN) in the prediction of energy consumption of air-source heat pump in retrofit residential housing
    Ye, K. K.
    Demirezen, Gulsun
    Fung, A. S.
    Janssen, E.
    INTERNATIONAL CONFERENCE ON SUSTAINABLE ENERGY AND GREEN TECHNOLOGY 2019, 2020, 463
  • [28] Water pipe network as a heat source for heat pump integrated into a district heating
    Jadwiszczak, Piotr
    Niemierka, Elzbieta
    INTERNATIONAL CONFERENCE ON ADVANCES IN ENERGY SYSTEMS AND ENVIRONMENTAL ENGINEERING (ASEE17), 2017, 22
  • [29] Maldistribution in air-water heat pump evaporators. Part 1: Effects on evaporator, heat pump and system level
    Mader, Gunda
    Palm, Bjorn
    Elmegaard, Brian
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 50 : 207 - 216
  • [30] Experimental Investigations on a Conventional Air-conditioner Working as Air-water Heat Pump
    Wang, Yu
    You, Yuwen
    Zhang, Zhigang
    PEEA 2011, 2011, 23