Ground Fault Section Positioning Algorithm of Active Distribution Network Based on Phase Transient Power Direction

被引:0
|
作者
Li J. [1 ]
He M. [1 ]
Huang S. [1 ]
Xu J. [2 ]
Cheng G. [2 ]
Zhou D. [2 ]
机构
[1] College of Electrical and Information Engineering, Hunan University, Changsha
[2] Weisheng Information Technology Co., Ltd., Changsha
来源
关键词
active distribution network; grounding fault location; phase transient power direction; single-phase ground; small current grounding system; transient phase voltage and phase current;
D O I
10.13336/j.1003-6520.hve.20230004
中图分类号
学科分类号
摘要
After the distributed power supply is connected to the distribution network, the accuracy of the grounding fault judgment algorithm using the phase current mutation is reduced. In order to solve the above problems, the grounding fault section positioning algorithm of active distribution network based on phase transient power direction is proposed. By establishing the equivalent model of grounding fault transient phase voltage and current of active distribution network, the analysis results show that the direction of the fault current flows from the bus to the line, and the fault line fault point downstream of the fault of the transient power absolute value is negative. According to the above characteristics, the grounding fault positioning device and phase transient power direction algorithm is designed. The simulation verification results show that this method, in which the small current grounding system at the neutral point of the distribution network is used, can be adopted to reliably judge and locate the grounding fault position in the distributed power input and exit, and different access quantity and position in the case of uneven current. Related research and its design can provide reference for the development and application of grounding fault positioning technology of active distribution network. © 2023 Science Press. All rights reserved.
引用
收藏
页码:3205 / 3215
页数:10
相关论文
共 20 条
  • [1] HUANG C, TANG T, JIANG Y J, Et al., Faulty feeder detection by adjusting the compensation degree of arc-suppression coil for distribution network, IET Generation Transmission & Distribution, 12, 4, pp. 807-814, (2018)
  • [2] CHU Tianxin, ZHANG Wenhai, QU Ke, Et al., Grounded incipient fault detection based on compound criterion in non-solidly grounding system, High Voltage Engineering, 48, 3, pp. 1022-1031, (2022)
  • [3] CUI Q S, EL-ARROUDI K, WENG Y., A feature selection method for high impedance fault detection, IEEE Transactions on Power Delivery, 34, 3, pp. 1203-1215, (2019)
  • [4] ZENG Xiangjun, WANG Zhan, YU Kun, Et al., Arc suppression device for actively reducing grounding fault phase voltage based on phase power supply feedback in distribution network and its application, High Voltage Engineering, 48, 9, pp. 3356-3366, (2022)
  • [5] TANG Tao, HUANG Chun, JIANG Yaqun, Et al., A method of fault line selection in resonant earthed system based on zero sequence impedance characteristic of lines, Transactions of China Electrotechnical Society, 31, 20, pp. 192-201, (2016)
  • [6] QI Zheng, ZHAO Xinyi, CHEN Yanbo, Single-phase grounding fault sensing technology in distribution network based on transient and steady state phase asymmetrical signals, High Voltage Engineering, 48, 4, pp. 1264-1276, (2022)
  • [7] WU Nan, SHI Mingming, ZHU Weiping, Et al., Application on transient recording fault indicator for single-phase grounding fault diagnosis, Southern Power System Technology, 15, 1, pp. 61-68, (2021)
  • [8] ZHAN Huiyu, LIU Keyan, SHENG Wanxing, Et al., Review and prospects of fault diagnosis and location method in active distribution network, High Voltage Engineering, 49, 2, pp. 660-671, (2023)
  • [9] XU Meng, ZOU Guibin, CHEN Ning, Et al., Energy-directional pilot protection based on leading-phase for active distribution network, Electric Power Automation Equipment, 37, 1, pp. 58-64, (2017)
  • [10] GANIVADA P K, JENA P., A fault location identification technique for active distribution system, IEEE Transactions on Industrial Informatics, 18, 5, pp. 3000-3010, (2022)