Performance analysis of three-stage liquid desiccant deep dehumidification processor driven by heat pump

被引:0
|
作者
Zhang, Haiqiang [1 ]
Liu, Xiaohua [1 ]
Jiang, Yi [1 ]
机构
[1] School of Architecture, Tsinghua University, Beijing 100084, China
关键词
Humidity control - Atmospheric temperature - Driers (materials) - Pipelines - Pumps - Liquids - Heat pump systems;
D O I
暂无
中图分类号
学科分类号
摘要
A new type of a heat pump driven three-stage lithium bromide liquid desiccant deep dehumidification processor is presented, which can dehumidify the outdoor humid air to a rather dry state, even when there is no available indoor exhaust air. The test results show that with an outdoor air temperature of 28 to 31°C and an outdoor air humidity ratio of 11 to 14 g/kg, the supply air temperature and the supply air humidity ratio are 1.6 to 2.6°C and 2.6 to 3.0 g/kg, respectively, and the coefficient of performance(COP)of the processor is 1.8.During the test, a liquid pipeline link problem leading to mixture losses of hot and cold liquid desiccants is found. These pipelines are modified. Then, the performance of the modified processor is investigated. And the experimental results show that with an outdoor air temperature of 25 to 32°C and an outdoor air humidity ratio of 18 to 21 g/kg, the supply air temperature and the supply air humidity ratio are 3.2 to 4.0°C and 3.4 to 3.6 g/kg, respectively, and the COP is 2.8.Finally, a mathematical model of the processor is established. The comparison of the simulation results and the test results of the processor exhibits that the pipeline modification improves the performance by about 20%. © right.
引用
收藏
页码:217 / 221
相关论文
共 50 条
  • [1] Performance Study on a Heat Pump Driven Three-stage Liquid Desiccant Deep Dehumidification Processor
    Zhang, Haiqiang
    Liu, Xiaohua
    Jiang, Yi
    [J]. 6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 679 - 686
  • [2] Performance optimization of heat pump driven liquid desiccant dehumidification systems
    Zhang, Tao
    Liu, Xiaohua
    Jiang, Yi
    [J]. ENERGY AND BUILDINGS, 2012, 52 : 132 - 144
  • [3] Performance of heat pump driven internally cooled liquid desiccant dehumidification system
    Liu, Jun
    Liu, Xiaohua
    Zhang, Tao
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2020, 205
  • [4] Performance optimization of a heat pump driven liquid desiccant dehumidification system using exergy analysis
    Zhang, Qinling
    Liu, Xiaohua
    Zhang, Tao
    Xie, Ying
    [J]. ENERGY, 2020, 204
  • [5] Performance investigation of a counter-flow heat pump driven liquid desiccant dehumidification system
    Xie, Ying
    Zhang, Tao
    Liu, Xiaohua
    [J]. ENERGY, 2016, 115 : 446 - 457
  • [6] Research on Flow Path Optimization of Liquid Desiccant Dehumidification System Driven by Heat Pump
    Qu, Hong-Shuo
    Zhang, Lun
    Zhang, Xiao-Song
    [J]. Kung Cheng Je Wu Li Hsueh Pao/Journal of Engineering Thermophysics, 2022, 43 (03): : 603 - 611
  • [7] Performance evaluation of a heat pump-driven liquid desiccant dehumidification system integrated with fresh air supply
    Li, Wenzhang
    Yin, Yonggao
    Wang, Yikai
    [J]. ENERGY AND BUILDINGS, 2022, 275
  • [8] Performance study of a heat pump driven and hollow fiber membrane-based two-stage liquid desiccant air dehumidification system
    Zhang, Ning
    Yin, Shao-You
    Zhang, Li-Zhi
    [J]. APPLIED ENERGY, 2016, 179 : 727 - 737
  • [9] Experimental investigation of a counter-flow heat pump driven liquid desiccant dehumidification system
    Liu, Xiaohua
    Xie, Ying
    Zhang, Tao
    Chen, Liangliang
    Cong, Lin
    [J]. ENERGY AND BUILDINGS, 2018, 179 : 223 - 238
  • [10] Operating characteristics and performance evaluation of carbon dioxide heat pump driven liquid desiccant dehumidification systems: A comparative study
    Cui, Qi
    Qu, Hongshuo
    Sun, Bo
    Gao, Enyuan
    Zhang, Xiaosong
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2022, 254