Shielding-failure protective effect of sideward rod on tower crossarm of UHVAC transmission line

被引:0
|
作者
Yu J. [1 ]
Zhou H. [1 ]
机构
[1] College of Electrical Engineering, Zhejiang University, Hangzhou
来源
| 1600年 / Electric Power Automation Equipment Press卷 / 36期
关键词
AC power transmission; Ground inclination angle; Lightning shielding; Sideward rod; Three-dimensional EGM; UHV power transmission; Wind deflection angle;
D O I
10.16081/j.issn.1006-6047.2016.07.008
中图分类号
学科分类号
摘要
In order to evaluate the protective effect of sideward lightning rod installed on the tower crossarm of UHVAC transmission line, its protective distance is calculated for three typical UHVAC towers in different conditions, which shows that, for better effect of shielding failure protection, the length of sideward rod installed on ZBS2 tower should be 6 m or more; in the conditions that the ground inclination angle is 0° and the wind deflection angle is less than 25°, the length of sideward rod installed on ZMP2 tower could be 4 m~5 m; if installed in the middle-phase crossarm of drum-shape tower, it could also be 4 m~5 m in the same conditions. © 2016, Electric Power Automation Equipment Press. All right reserved.
引用
收藏
页码:47 / 52
页数:5
相关论文
共 17 条
  • [11] Lan Z., Zhao C., Ruan J., Analysis and calculation of submarine cable-overhead line lightning over- voltage, Electric Power Automation Equipment, 34, 10, pp. 133-137, (2014)
  • [12] Qian G., Wang X., Xu X., Et al., The variation of shielding failure probability along transmission line, High Voltage Engineering, 25, 1, pp. 23-25, (1999)
  • [13] Armstrong H.R., Whitehead E.R., Field and analytical studies of transmission line shielding, IEEE Transactions on Power Apparatus and System, 87, 1, pp. 270-281, (1968)
  • [14] Brown G.W., Whitehead E.R., Field and analytical studies of transmission line shielding: part II, IEEE Transactions on Power Apparatus and System, 88, 5, pp. 617-626, (1969)
  • [15] IEEE guide for improving the lightning performance of transmission lines: IEEE std 1234-1997, (1997)
  • [16] Wang M., Zhang Z., Teng J., Et al., Lightning shielding failure protection for 1 000 kV single circuit UHVAC transmission line, Power System Technology, 32, 1, pp. 1-4, (2008)
  • [17] Wang S., Wu G., Fan J., Et al., Study on flashover of suspension insulator string caused by windage yaw in 500 kV transmission lines, Power System Technology, 32, 9, pp. 65-69, (2008)