A distance protection scheme not affected by transient characteristic of capacitor voltage transformer for HV long transmission line

被引:0
|
作者
机构
[1] Jiao, Zaibin
[2] Qi, Qian
[3] Yang, Liming
[4] Wang, Youyin
[5] Ning, Rong
来源
Jiao, Zaibin | 1600年 / Power System Technology Press卷 / 38期
关键词
Electric power transmission - Power transformers - Surge protection - Electric power transmission networks - Extraction - Variable speed transmissions - Transformer protection - Electric fault currents - Power quality - Electric power system protection;
D O I
10.13335/j.1000-3673.pst.2014.11.036
中图分类号
学科分类号
摘要
Affected by transient characteristic of capacitor voltage transformer (CVT), the distance protection for HV transmission line is easily to mal-operate due to transient overreach, thus the secure and stable operation of power grid is affected. A new distance protection scheme that is not affected by the transient characteristics of CVT is proposed and its principle is as following: firstly, on the basis that the CVT can transmit and transform power frequency phasor, by means of the matrix pencil based accurate power frequency phasor extraction method the power frequency phasors of voltage and current at the position where the protection is installed are calculated; secondly, the voltage and current at the position of the long distance transmission line, where the protection is set, are calculated by Bergeron model; finally, coordinating with directional element and taking the setting point as the observation point, the fault point is located by traditional distance protection algorithm. The proposed principle is not affected by transient characteristic of CVT and the impacts of distributed parameters of the long distance transmission line are taken into account, thus the proposed distance protection scheme possesses a better performance, and the effectiveness of the proposed algorithm is validated by simulation results. ©, 2014, Power System Technology Press. All right reserved.
引用
收藏
相关论文
共 50 条
  • [1] Adaptive distance protection scheme with quadrilateral characteristic for extremely high-voltage/ultra-high-voltage transmission line
    Ma, Jing
    Xiang, Xiaoqiang
    Li, Pei
    Deng, Zhuojun
    Thorp, James S.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2017, 11 (07) : 1624 - 1633
  • [2] Improved Differential Protection Scheme for Long Distance UHVDC Transmission Line
    Zheng, Xiaodong
    Tai, Nengling
    Thorp, James S.
    Yang, Xia
    2014 IEEE PES GENERAL MEETING - CONFERENCE & EXPOSITION, 2014,
  • [3] Natural frequency based protection scheme for long distance transmission line
    Huang, Shaofeng
    Wang, Xingguo
    Liu, Qiankuan
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2008, 32 (08): : 59 - 63
  • [4] A Transient Protection Scheme for HVDC Transmission Line
    Zheng, Xiaodong
    Tai Nengling
    Yang Guangliang
    Ding Haoyin
    IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (02) : 718 - 724
  • [5] NOVEL DESIGNS IN DISTANCE PROTECTION FOR HV TRANSMISSION NETWORKS - THE MICROMHO SCHEME
    WELLER, GC
    CHEETHAM, WJ
    GEC-JOURNAL OF SCIENCE & TECHNOLOGY, 1983, 49 (01): : 3 - 12
  • [6] A New Adaptive Distance Protection Scheme for a Transmission Line
    Ma, Jing
    Yan, Xin
    Ma, Wei
    Sun, Lvyi
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2016, 44 (01) : 1 - 17
  • [7] Transmission Line Distance Protection Under Current Transformer Saturation
    Zheng, Yuping
    Wu, Tonghua
    Hong, Feng
    Yao, Gang
    Chai, Jimin
    Wei, Zhinong
    JOURNAL OF MODERN POWER SYSTEMS AND CLEAN ENERGY, 2021, 9 (01) : 68 - 76
  • [8] Transmission Line Distance Protection Under Current Transformer Saturation
    Yuping Zheng
    Tonghua Wu
    Feng Hong
    Gang Yao
    Jimin Chai
    Zhinong Wei
    Journal of Modern Power Systems and Clean Energy, 2021, 9 (01) : 68 - 76
  • [9] The Transient Distance Protection on Wind Farm Transmission Line with Crowbar Protection
    Zhang, Xingyu
    Lu, Yuping
    Shi, Dongmin
    PROCEEDINGS OF 2017 2ND INTERNATIONAL CONFERENCE ON POWER AND RENEWABLE ENERGY (ICPRE), 2017, : 366 - 371
  • [10] Transient Protection Scheme of HVDC Transmission Line Based on Time-domain Voltage Ratio
    Chen X.
    Li H.
    Gu G.
    Liang Y.
    Wang G.
    Li, Haifeng (lihf@scut.edu.cn), 1600, Automation of Electric Power Systems Press (44): : 62 - 69