Wind farm protection

被引:0
|
作者
Qureshi, Waqar A. [1 ]
Nair, Nirmal-Kumar C. [1 ]
机构
[1] Department of Electrical and Computer Engineering, Science Centre, University of Auckland, 38 Princes Street, Building 303, Auckland 1142, New Zealand
关键词
Electric power transmission networks - Electric power transmission - Quality control - Electric utilities - Electric equipment protection - Electric power system protection - Turbogenerators - Electric fault currents - Wind farm - Electric power system interconnection;
D O I
10.1007/978-981-4585-30-9_12
中图分类号
学科分类号
摘要
Transmission system operation with wind generators has been well analyzed for issues like forecasting, reliability, control, power quality, and fault ride through (FRT) impacts following large-scale integration. However, there are still no standardized protection schemes for wind farms such as those practiced for the protection of conventional generation plants. Wind generators' collective response under high penetration scenarios needs special attention especially under abnormal operations such as grid disturbances and faults. During abnormal grid situations like faults, protection requirements for wind farms depend on a variety of factors. Different wind generation technologies exhibit different dynamic characteristics compared to conventional synchronous generator plants. Network characteristics and their interaction with available wind technologies also impact the fault behavior. This chapter first comprehensively reviews the integration characteristics and criteria for three different wind generator technologies connected to high voltage (HV) transmission systems. Aspects such as selection of time step and impact of additional controls such as crowbar protection are also discussed with their possible impacts on fault current estimation. A case study in Dig SILENT® Power Factory has been developed to assess and compare the fault response of wind generator technology types. The response of each WTG type is generalized and analyzed in time domain to determine the number of electrical frequency cycles before the fault current reaches to steady-state value. Based on the estimated number of cycles and in the scenario of weaker interconnecting grids, protection schemes performance and protection relay operation are mainly assessed for each wind turbine generator (WTG) type. Technical challenges and difficulties are also highlighted before concluding. © Springer Science+Business Media Singapore 2014.
引用
收藏
页码:311 / 329
相关论文
共 50 条
  • [21] Crowbar protection impact on wind farm behaviour during grid disturbance
    Beniuga, Razvan
    Istrate, Marcel
    Beniuga, Oana
    2017 7TH INTERNATIONAL CONFERENCE ON MODERN POWER SYSTEMS (MPS), 2017,
  • [22] Adaptive Protection Schemes for Feeders with the Penetration of SEIG based Wind Farm
    Rones, Arthi Sahaya, V
    Vittal, K. P.
    2013 IEEE INNOVATIVE SMART GRID TECHNOLOGIES - ASIA (ISGT ASIA), 2013,
  • [23] Dynamic modeling of Al-Zaafarana wind farm for protection applications
    Kawady, Tamer
    Mansour, Naema
    Osheiba, Aly
    Taalab, Abd El-Maksoud
    2008 12TH INTERNATIONAL MIDDLE EAST POWER SYSTEM CONFERENCE, VOLS 1 AND 2, 2008, : 322 - 326
  • [24] Transient current similarity based protection for wind farm transmission lines
    Jia, Ke
    Li, Yanbin
    Fang, Yu
    Zheng, Liming
    Bi, Tianshu
    Yang, Qixun
    APPLIED ENERGY, 2018, 225 : 42 - 51
  • [25] Wind farm transmission transformer protection based on synchrosqueezed wavelet transform
    Yang X.
    Qu Y.
    Song H.
    Huang K.
    Fan X.
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2022, 50 (12): : 22 - 32
  • [26] Adaptive differential protection scheme for wind farm integrated power network
    Prasad, Ch Durga
    Biswal, Monalisa
    Abdelaziz, Almoataz Y.
    ELECTRIC POWER SYSTEMS RESEARCH, 2020, 187 (187)
  • [27] A Novel Protection Method of Collecting Power Lines in PMSG Wind Farm
    Song, Guobing
    Wang, Xiaobo
    Chang, Zhongxue
    Tang, Jisi
    Liu, Peiyao
    2016 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2016, : 2086 - 2090
  • [28] Impact Analyses of Wind Farm on Performances of Transmission Line Relay Protection
    Jin WANG Baohui ZHANG School of Electrical EngineeringXian Jiaotong UniversityXian China
    电力系统自动化, 2012, 36 (08) : 148 - 153
  • [29] Impact analyses of wind farm on performances of transmission line relay protection
    Wang, Jin
    Zhang, Baohui
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2012, 36 (08): : 148 - 153
  • [30] A Differential Protection Scheme for Tapped Transmission line Containing UPFC and Wind farm
    Tripathy, L. N.
    Jena, Manas Kumar
    Samantaray, S. R.
    Dash, D. R.
    2014 IEEE STUDENTS' TECHNOLOGY SYMPOSIUM (IEEE TECHSYM), 2014, : 319 - 324