Subsynchronous harmonic phasor detection in a renewable energy grid-connected system

被引:0
|
作者
Huang X. [1 ]
Luo P. [1 ]
Gong J. [1 ]
Xie L. [1 ]
Yang C. [2 ]
机构
[1] School of Electrical Engineering, Shanghai University of Electric Power, Shanghai
[2] College of Electronics and Information Engineering, Tongji University, Shanghai
基金
中国国家自然科学基金;
关键词
All-phase FFT; Phase difference correction; Phasor detection; Renewable energy grid-connected; Subsynchronous oscillation;
D O I
10.19783/j.cnki.pspc.190942
中图分类号
学科分类号
摘要
The subsynchronous harmonics generated by a renewable energy collection area will affect the safety and stability of a power grid, and the harmonic detection accuracy of the traditional Fourier algorithm is easily affected by spectrum leakage and the fence effect. In order to improve the detection accuracy of subsynchronous harmonics, a new algorithm based on the Nuttall window and all-phase Fourier analysis (apFFT) is proposed. By dividing the sampled data into N segments and adding 4 terms 5 orders Nuttall windows twice, the pre-processed N-point data segments are obtained and FFT is performed. Further, based on the square relationship of amplitude between apFFT and traditional FFT and the "Phase invariance" of apFFT, the apFFT spectrum analysis results of amplitude and frequency are corrected. Compared with the eigenvalue analysis method and the interpolation correction FFT method, this method improves the accuracy of subsynchronous harmonic detection while maintaining the speed of FFT. The simulation results verify the effectiveness of the proposed method. © 2020, Power System Protection and Control Press. All right reserved.
引用
收藏
页码:38 / 44
页数:6
相关论文
共 25 条
  • [11] LI Kuan, LI Xingyuan, ZHAO Rui, Detection of subsynchronous oscillation in HVDC transmission system based on improved matrix pencil method, Power System Technology, 36, 4, pp. 128-132, (2012)
  • [12] ZHANG Chao, WANG Weiqing, QIU Yanjiang, Et al., Subsynchronous harmonic detection method in regions with large scale wind power paralleled in grid, High Voltage Engineering, 45, 7, pp. 2194-2202, (2019)
  • [13] XIE Xiaorong, WANG Yin, LIU Huakun, Et al., Detection method for sub-synchronous and super-synchronous harmonic phasors in power system, Automation of Electric Power Systems, 40, 21, pp. 189-194, (2016)
  • [14] WANG Yifei, LI Yunwei, A grid fundamental and harmonic component detection method for single-phase systems, IEEE Transactions on Power Electronics, 28, 5, pp. 2204-2213, (2013)
  • [15] WANG Maohai, QI Xia, Fast online detection method for power system sub-synchronous oscillation components, Automation of Electric Power Systems, 40, 18, pp. 149-154, (2016)
  • [16] XU Yan, ZHANG Xiaoming, WANG Yu, Et al., A new method of spectrum analysis based on DFT, Power System Protection and Control, 39, 11, pp. 38-43, (2011)
  • [17] ZHANG Fusheng, GENG Zhongxing, GE Yaozhong, FFT algorithm with high accuracy for harmonic analysis in power system, Proceedings of the CSEE, 19, 3, pp. 63-66, (1999)
  • [18] MA Renzheng, CHEN Mingkai, An adaptive sampling algorithm for reducing spectrum leakage, Automation of Electric Power Systems, 26, 7, pp. 55-58, (2002)
  • [19] WEN He, TENG Zhaosheng, QING Baiyuan, Hanning self-convolution windows and its application to harmonic analysis, Transactions of China Electrotechnical Society, 24, 2, pp. 164-169, (2009)
  • [20] HOU Zhengxin, WANG Zhaohua, YANG Xi, Design and implementation of all phase DFT digital filter, Acta Electronica Sinica, 31, 4, pp. 1-4, (2003)