Analysis of Subsynchronous Oscillation Characteristics of D-PMSG Integrated With LCC-HVDC System

被引:0
|
作者
Gao B. [1 ]
Cui Y. [1 ]
Li Y. [2 ]
Zhao F. [3 ]
Liu Y. [4 ]
Shao B. [1 ]
Zhao S. [1 ]
机构
[1] Hebei Key Laboratory of Distributed Energy Storage and Micro-grid (North China Electric Power University), Baoding
[2] North China Electric Power Research Institute, Xicheng District, Beijing
[3] North China Branch of State Grid Corporation of China, Xicheng District, Beijing
[4] State Grid Suzhou Power Supply Company, Suzhou
关键词
Direct- drive permanent magnet synchronous generator (D-PMSG); Line-commutated-converter based high voltage direct current (LCC-HVDC); Modular block modeling method; Participation factor analysis; Sub-synchronous oscillation (SSO);
D O I
10.13334/j.0258-8013.pcsee.202537
中图分类号
学科分类号
摘要
When the direct-drive permanent magnet synchronous generator (D-PMSG) is located near the line-commutated-converter based high voltage direct current (LCC-HVDC) rectifier station, the sub-synchronous oscillation (SSO) characteristics of the system are still unclear, and relevant research needs to be carried out. In response to above the problems, this paper used the modular modeling method to establish a small signal model of the D-PMSG integrated with LCC-HVDC system, and the participation of D-PMSG and LCC-HVDC in the system SSO mode was studied with eigenvalues and participation factors. The eigenvalues were used to analyze the influence of system parameters on SSO damping. Research results showed that there was an SSO mode in which D-PMSG and LCC-HVDC participated together, and the LCC-HVDC connection provided negative damping for the system SSO. When the D-PMSG transmission line impedance and the integral coefficient of the outer loop of the GSC controller increased, the damping of the SSO mode decreased. When the proportional coefficient of D-PMSG GSC controller outer loop and D-PMSG DC side capacitance and wind speed of D-PMSG and LCC-HVDC constant current controller increased, SSO mode damping increased. Based on the PSCAD/EMTDC time domain simulation results, the correctness of the theoretical analysis was verified. © 2022 Chin. Soc. for Elec. Eng.
引用
收藏
页码:2084 / 2095
页数:11
相关论文
共 30 条
  • [11] GAO Feng, HE Qifei, HAO Zhiguo, Et al., The research of sub synchronous oscillation in PMSG wind farm, 2016 IEEE PES Asia-Pacific Power and Energy Engineering Conference(APPEEC), pp. 1883-1887, (2016)
  • [12] ALAWASA K M, MOHAMED Y A R I, Xu W., Modeling, analysis, and suppression of the impact of full-scale wind-power converters on subsynchronous damping, IEEE Systems Journal, 7, 4, pp. 700-712, (2013)
  • [13] CHEN Wuhui, YU Xiao, HAN Xiaoqing, Et al., Analysis of forced SSOs excited by subsynchronous interharmonics from DPMSG-based wind farms, IEEE Transactions on Sustainable Energy, 12, 2, pp. 978-989, (2021)
  • [14] REN Bixing, DU Wenjuan, WANG Haifeng, Et al., Influence of PLL control on sub-synchronous oscillation stability of grid-connected PMSG: control parameter safety region, Electric Power Automation Equipment, 40, 9, pp. 142-149, (2020)
  • [15] HAO Yafeng, LIANG Jun, WANG Kewen, Et al., Influence of active power output of full-converter wind farm on subsynchronous oscillation characteristics and parameter adjustment in weak grid, Power System Technology, 45, 7, pp. 2752-2765, (2021)
  • [16] AMIN M, MOLINAS M, LYU Jing, Oscillatory phenomena between wind farms and HVDC systems: the impact of control, Proceedings of 2015 IEEE 16th Workshop on Control and Modeling for Power Electronics(COMPEL), pp. 1-8, (2015)
  • [17] QIAO Dengke, WANG Zizhe, SUN Yikai, Et al., Analysis of subsynchronous oscillation in the system inteconnected with offshore wind farm by VSC-HVDC based on impedance method, 2019 9th International Conference on Power and Energy Systems(ICPES), pp. 1-5, (2019)
  • [18] AMIN M, MOLINAS M., Understanding the origin of oscillatory phenomena observed between wind farms and HVDC systems, IEEE Journal of Emerging and Selected Topics in Power Electronics, 5, 1, pp. 378-392, (2017)
  • [19] CHEN Baoping, LIN Tao, CHEN Rusi, Et al., Analysis on characteristics of sub/super-synchronous oscillation caused by grid-connected direct-drive wind farm via VSC-HVDC system, Automation of Electric Power Systems, 42, 22, pp. 44-51, (2018)
  • [20] SHAO Bingbing, ZHAO Shuqiang, PEI Jikun, Et al., Subsynchronous oscillation characteristic analysis of grid-connected DDWFs via VSC-HVDC system, Power System Technology, 43, 9, pp. 3344-3352, (2019)