Protection Method of Flexible DC Power Distribution Network Based on Grounding Mode with High Resistor and Arrester in Parallel

被引:0
|
作者
Jia Y. [1 ]
Gao S. [2 ,3 ]
Si X. [1 ]
Shi Y. [4 ]
Zhan X. [5 ]
Wang J. [2 ,3 ]
机构
[1] Electric Power Research Institute of State Grid Jiangsu Electric Power Co., Ltd., Nanjing
[2] School of Electrical Engineering, Southeast University, Nanjing
[3] Jiangsu Provincial Key Laboratory of Smart Grid Technology and Equipment, Southeast University, Nanjing
[4] NR Electric Co., Ltd., Nanjing
[5] Yangzhou Power Supply Company of State Grid Jiangsu Electric Power Co., Ltd., Yangzhou
关键词
Arrester; Flexible DC power distribution network; Grounding; Overvoltage; Protection;
D O I
10.7500/AEPS20190430031
中图分类号
学科分类号
摘要
To solve the difficult problem of monopolar grounding fault detection in flexible medium-voltage DC power distribution network, this paper proposes a new grounding mode with high resistor and arrester in parallel and a protection strategy including adaptive amplification factor. Firstly, advantages and disadvantages of the existing grounding modes in flexible DC distribution network are discussed. A new grounding mode with high resistor and arrester in parallel via the neutral point of the coupling transformer is proposed. Secondly, the overvoltage mechanism and fault characteristics of the new grounding mode are analyzed by theoretical derivation with AC/DC grounding faults. According to voltage and current characteristics in different fault conditions, the DC line protection strategy is developed. It realizes the accurate and rapid fault identification of differential protection with faults in DC network. Finally, the effectiveness of the new grounding mode and the reliability of the proposed protection method are verified by simulation example. © 2020 Automation of Electric Power Systems Press.
引用
收藏
页码:166 / 173
页数:7
相关论文
共 28 条
  • [11] He Q., Han Y., Ruan Y., Et al., Research on grounding scheme for ±10 kV flexible DC power distribution system, Guangdong Electric Power, 28, 12, pp. 109-114, (2015)
  • [12] He Q., Han Y., Zhao Y., Et al., Overvoltage and insulation coordination of ± 10 kV DC distribution system, Southern Power System Technology, 10, 4, pp. 16-22, (2016)
  • [13] Su Y., Hu L., Xu F., Et al., Research on switching overvoltage in flexible DC distribution network, Power System Technology, 42, 10, pp. 3196-3203, (2018)
  • [14] Wang Y., Zhang B., Fan X., Fast protection scheme for overhead transmission lines of VSC-based HVDC grid, Automation of Electric Power Systems, 40, 21, pp. 13-19, (2016)
  • [15] Sneath J., Rajapakse A.D., Fault detection and interruption in an earthed HVDC grid using ROCOV and hybrid DC breakers, IEEE Transactions on Power Delivery, 31, 3, pp. 973-981, (2016)
  • [16] Song G., Jin X., Ran M., Et al., Pilot protection for VSC-HVDC transmission lines based on shunt capacitance parameter identification, Automation of Electric Power Systems, 37, 15, pp. 76-82, (2013)
  • [17] Liu Q., Song G., A novel pilot protection for HVDC transmission lines using mean current error control characteristics, Proceedings of the CSEE, 36, 8, pp. 2159-2167, (2016)
  • [18] Yao W., Xing D., Wu J., Et al., Study on ultra-high-speed protection method of flexible HVDC grid, Power System Technology, 41, 6, pp. 1710-1718, (2017)
  • [19] Wang Y., Fan X., Zhang B., The analytical analysis and protection setting of traveling wave protection in VSC-HVDC grid, Proceedings of the CSEE, 39, 11, pp. 3201-3212, (2019)
  • [20] Li H., Xie J., Wang Y., Et al., Adaptive setting and performance optimization of protection devices on extra-high voltage transmission line, Automation of Electric Power Systems, 42, 17, pp. 148-154, (2018)