Protection Method of Flexible DC Power Distribution Network Based on Grounding Mode with High Resistor and Arrester in Parallel

被引:0
|
作者
Jia Y. [1 ]
Gao S. [2 ,3 ]
Si X. [1 ]
Shi Y. [4 ]
Zhan X. [5 ]
Wang J. [2 ,3 ]
机构
[1] Electric Power Research Institute of State Grid Jiangsu Electric Power Co., Ltd., Nanjing
[2] School of Electrical Engineering, Southeast University, Nanjing
[3] Jiangsu Provincial Key Laboratory of Smart Grid Technology and Equipment, Southeast University, Nanjing
[4] NR Electric Co., Ltd., Nanjing
[5] Yangzhou Power Supply Company of State Grid Jiangsu Electric Power Co., Ltd., Yangzhou
关键词
Arrester; Flexible DC power distribution network; Grounding; Overvoltage; Protection;
D O I
10.7500/AEPS20190430031
中图分类号
学科分类号
摘要
To solve the difficult problem of monopolar grounding fault detection in flexible medium-voltage DC power distribution network, this paper proposes a new grounding mode with high resistor and arrester in parallel and a protection strategy including adaptive amplification factor. Firstly, advantages and disadvantages of the existing grounding modes in flexible DC distribution network are discussed. A new grounding mode with high resistor and arrester in parallel via the neutral point of the coupling transformer is proposed. Secondly, the overvoltage mechanism and fault characteristics of the new grounding mode are analyzed by theoretical derivation with AC/DC grounding faults. According to voltage and current characteristics in different fault conditions, the DC line protection strategy is developed. It realizes the accurate and rapid fault identification of differential protection with faults in DC network. Finally, the effectiveness of the new grounding mode and the reliability of the proposed protection method are verified by simulation example. © 2020 Automation of Electric Power Systems Press.
引用
收藏
页码:166 / 173
页数:7
相关论文
共 28 条
  • [1] Jiang D., Zheng H., Research status and developing prospect of DC distribution network, Automation of Electric Power Systems, 36, 8, pp. 98-104, (2012)
  • [2] Zhao B., Zhao Y., Wang Y., Et al., Energy internet based on flexible medium-voltage DC distribution, Proceedings of the CSEE, 35, 19, pp. 4843-4851, (2015)
  • [3] Liu L., Ye Z., Fu L., Et al., Research & development status and prospects of fast DC circuit breakers, Proceedings of the CSEE, 37, 4, pp. 966-978, (2017)
  • [4] Mohammadpour A., Parsa L., Todorovic M.H., Et al., Series-input parallel-output modular-phase DC-DC converter with soft-switching and high-frequency isolation, IEEE Transactions on Power Electronics, 31, 1, pp. 111-119, (2016)
  • [5] Xu Z., Flexible HVDC System, (2013)
  • [6] De Kerf K., Srivastava K., Reza M., Et al., Wavelet-based protection strategy for DC faults in multi-terminal VSC HVDC systems, IET Generation, Transmission & Distribution, 5, 4, (2011)
  • [7] Yang J., Fletcher J.E., O'Reilly J., Short-circuit and ground fault analyses and location in VSC-based DC network cables, IEEE Transactions on Industrial Electronics, 59, 10, pp. 3827-3837, (2012)
  • [8] Li R., Luo F., Jiao Z., Grounding mode research of MV DC distribution system, Power System Technology, 42, 8, pp. 2594-2603, (2018)
  • [9] Wu J., Wu D., Zhu J., Et al., Grounding method design of multi-terminal flexible DC distribution, Proceedings of the CSEE, 37, 9, pp. 2551-2561, (2017)
  • [10] Dai Z., Ge H., Yan S., Et al., Effects of grounding mode on fault characteristics in flexible DC distribution system, Power System Technology, 41, 7, pp. 2353-2364, (2017)