Single-pole ground selection method for DC distribution networks based on zero-mode current correlation

被引:0
|
作者
Zuo P. [1 ]
Qin W. [1 ]
Xia F. [2 ]
Chen X. [1 ]
Yang L. [1 ]
机构
[1] Shanxi Key Laboratory of Power System Operation and Control, Taiyuan University of Technology, Taiyuan
[2] State Grid Jinzhong Taigu District Power Supply Company, Jinzhong
关键词
correlation; distribution system; modular multilevel converter; unipolar earth fault; zero mode current;
D O I
10.19783/j.cnki.pspc.211262
中图分类号
学科分类号
摘要
The most common fault of a flexible DC distribution system is the single-pole grounding fault. After the occurrence of such a fault, the system will have voltage imbalance between the fault and non-fault poles. This poses a threat to the safe and stable operation of the system, and demonstrates the need for the speed and reliability of the protection scheme. This paper first analyzes the fault current characteristics of a flexible DC distribution system after a single-pole grounding fault, and then verifies the correlation of zero-mode current components at both ends of the line when the fault occurs. Finally, a single-pole grounding line selection scheme based on the correlation of zero-mode current at both ends of the line is proposed. This protection scheme makes full use of the inherent transient characteristics of the system after failure and does not need to use boundary elements to construct boundary characteristics. A modular multilevel converter (MMC)-based electromagnetic simulation model of a flexible DC distribution system is built on a real time digital simulator (RTDS) to verify the effectiveness of the scheme. The results show that the proposed route selection scheme can identify fault lines quickly and reliably, and has a strong capability to withstand transition resistance, noise and transmission delay, and is not affected by AC side faults. © 2022 Power System Protection and Control Press. All rights reserved.
引用
收藏
页码:86 / 96
页数:10
相关论文
共 31 条
  • [1] LIANG Handong, GAO Yuqun, HOU Ting, Et al., Study on the influence of load fluctuation on overvoltage and overcurrent of a VSC-DC distribution system, Power System Protection and Control, 48, 13, pp. 56-62, (2020)
  • [2] SHANGGUAN Xin, QIN Wenping, XIA Fuliang, Et al., Pole-to-ground fault protection scheme for MMC multi-terminal flexible DC distribution network based on Pearson correlation of transient voltage, High Voltage Engineering, 46, 5, pp. 1740-1749, (2020)
  • [3] HE Jinghan, HE Keao, CHEN Meng, Et al., Review of protection and fault handling for a flexible DC grid, Protection and Control of Modern Power Systems, 5, 2, pp. 151-165, (2020)
  • [4] LI Weifeng, WANG Chao, XUE Yongduan, Et al., A flexible DC distribution network line unipolar grounding protection method based on transient power direction, Power System Protection and Control, 49, 23, pp. 1-10, (2021)
  • [5] YANG X, XUE Y, WEN P., Comprehensive understanding of DC pole-to-pole fault and its protection for modular multilevel converters, High Voltage, 3, 4, pp. 246-254, (2018)
  • [6] LIN Xiangning, LIU Qi, FAN Lixiang, Et al., A novel pilot protection for VSC-MTDC based on correlation analysis, Power System Protection and Control, 48, 13, pp. 45-55, (2020)
  • [7] LI Yan, HUANG Yu, GONG Yanfeng, Et al., Analysis on overvoltage mechanism of DC line fault in flexible DC grid, Automation of Electric Power Systems, 44, 5, pp. 146-153, (2020)
  • [8] HAN Yongxia, FENG Shuaisong, GAO Yuqun, Et al., Review on research of overvoltage and overcurrent protection for flexible DC distribution system, Guangdong Electric Power, 33, 12, pp. 81-89, (2020)
  • [9] LI B, LI C, GUO F., Overcurrent protection coordination in a power distribution network with the active superconductive fault current limiter, IEEE Transactions on Applied Superconductivity, 24, 5, pp. 1-4, (2014)
  • [10] WANG Yanting, ZHANG Baohui, FAN Xinkai, Fast protection scheme for overhead transmission lines of VSC-based HVDC grid, Automation of Electric Power Systems, 40, 21, pp. 13-19, (2016)