Restraint of Start-up Inrush Current of Three-phase VSI Based on Virtual Damping Control

被引:0
|
作者
He K. [1 ,2 ]
Su H. [1 ,2 ]
Jiang K. [1 ]
Zeng H. [1 ]
机构
[1] School of Automation & Electrical Engineering, Lanzhou Jiaotong University, Lanzhou
[2] Rail Transit Electrical Automation Engineering Laboratory of Gansu Province, Lanzhou
来源
基金
中国国家自然科学基金;
关键词
Dynamic current quality; Grid-connected inverter; Inrush current; Start-up process; Virtual damping;
D O I
10.13336/j.1003-6520.hve.20200331038
中图分类号
学科分类号
摘要
There exists a start-up inrush current problem during the grid-connection period within the three-phase voltage-source inverters(VSI). Consequently, we propose a new method to suppress the inrush current effectively based on the virtual damping control. Firstly, a mathematical model is established based on the dq coordinate frame, and it is recognized that the primary cause of inrush current is the decrement in the damping ratio during the grid-connection period. Then, the detailed design process of the virtual damping control method is given, and the correctness and effectiveness of the proposed method are verified by simulation and experiments. The results show that the inrush current can be more than twice the rated current before adding virtual damping, the grid connection without inrush current can be realized after adding virtual damping, and it can also improve the robust stability of the system, the dynamic current quality, and equipment safety in operation. © 2020, High Voltage Engineering Editorial Department of CEPRI. All right reserved.
引用
收藏
页码:1068 / 1076
页数:8
相关论文
共 27 条
  • [21] Wang Q., Zhang X., Zhang Y., Et al., Suppression of impulse current in high power grid-connected inverter, Journal of Naval University of Engineering, 25, 6, pp. 109-112, (2013)
  • [22] Yang L., Wang C., Lu Z., Et al., The method of pre-synchronized grid-connection of synchronverter, Power System Technology, 38, 11, pp. 3103-3108, (2014)
  • [23] Xiong L., Liu X., Zhuo F., Et al., Small-signal modeling of photovoltaic power generation system and global optimal design for its controller parameters, Power System Technology, 38, 5, pp. 1234-1241, (2014)
  • [24] Tang Y., Electromechanics, pp. 113-115, (2011)
  • [25] Fritz S., Lars E.N., Grid connected converters for photovoltaic state of the art, ideas for improvement of transformerless inverters, NORPIE/2008, Nordic Workshop on Power and Industrial Electronics, pp. 1-6, (2008)
  • [26] Lu J., Automatic Control Theory, pp. 53-57, (2013)
  • [27] Liu L., Stability analysis and enhancing control strategy of grid-connected inverter under weak grid, pp. 25-37, (2018)