Fast Calculation of the Impedence Using Tensor-Based FEM for Evaluating Very Fast Transient Overvoltage in GIS

被引:0
|
作者
Zhang, Li [1 ]
Zhuo, Ran [2 ,3 ]
Pan, Shenggui [4 ]
Luo, Yan [2 ,3 ]
Fu, Kelin [5 ]
Zhang, Junjie [1 ]
Wang, Yu [1 ]
机构
[1] Elect Power Res Inst Guizhou Power Grid Co Ltd, Guiyang, Peoples R China
[2] Elect Power Res Inst China Southern Power Grid, Guangzhou, Peoples R China
[3] CSG, United Lab Adv Elect Mat & Equipment Support Tech, Guangzhou, Peoples R China
[4] Liupanshui Power Supply Bur Guizhou Power Grid Co, Liupanshui, Peoples R China
[5] Zunyi Power Supply Bur Guizhou Power Grid Co Ltd, Zunyi, Peoples R China
关键词
Impedance; GIS; Accelerated computing;
D O I
10.1007/978-981-97-0865-9_56
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
To solve the VFTO in GIS, it is necessary to perform the earth and GIS interconnection system, and then calculate the impedance to earth. The GIS interconnection system is rarely considered in current studies. To solve the problem of large computation time and meshes, a semi-analytical method is used to decompose the region into two sub-regions and calculate the sub-regions by finite element method and analytical solution method respectively, while introducing tensor calculation in the finite element part greatly reduces the computation time. The results are calculated in case of single-phase and three-phase, meanwhile, the frequency domain results for the overall system were analyzed. The approach proposed in this paper can be used to solve the problem of GIS impedance to ground, and has a large improvement in computational performance.
引用
收藏
页码:518 / 526
页数:9
相关论文
共 50 条
  • [21] Influence of the Switching Speed of the Disconnector on Very Fast Transient Overvoltage
    Shu Yinbiao
    Han Bin
    Lin Ji-Ming
    Chen Weijiang
    Ban Liangeng
    Xiang Zutao
    Chen Guoqiang
    IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (04) : 2080 - 2084
  • [22] Influence of Switching Properties of the Disconnector on Very Fast Transient Overvoltage
    Zhan, Huamao
    Duan, Shaofeng
    Yao, Linzhi
    Zhao, Lin
    2017 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2017, : 412 - 416
  • [23] Measurement of very fast transient overvoltages in GIS
    Shi, Baozhuang
    Zhang, Wenyuan
    Qiu, Yuchang
    Wang, Yun
    Dai, Youfu
    Gaodianya Jishu/High Voltage Engineering, 24 (01): : 17 - 18
  • [24] Electric Field Distribution of UHVAC Basin-type Insulator with Very Fast Transient Overvoltage in GIS
    Wu, Zehua
    Wang, Haoran
    Tian, Huidong
    Shi, Ran
    Zhou, Shiyi
    Peng, Zongren
    Zhang, Pengfei
    2018 12TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS (ICPADM 2018), 2018, : 570 - 573
  • [25] SUPPRESSION OF FAST TRANSIENT OVERVOLTAGE DURING GAS DISCONNECTOR SWITCHING IN GIS
    OZAWA, J
    YAMAGIWA, T
    HOSOKAWA, M
    TAKEUCHI, S
    KOZAWA, H
    IEEE TRANSACTIONS ON POWER DELIVERY, 1986, 1 (04) : 194 - 201
  • [27] Statistical Law for Parameters of Very Fast Transient Overvoltage in UHV Substations
    Zhang, Zihao
    Zhan, Huamao
    Ma, Yuhui
    2016 IEEE PES ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2016, : 983 - 986
  • [28] Suppressing Resonance in Transformer Winding Under Very Fast Transient Overvoltage
    Babaei, Mehdi
    Abu-Siada, A.
    Babaei, Maziar
    2016 IEEE INNOVATIVE SMART GRID TECHNOLOGIES - ASIA (ISGT-ASIA), 2016, : 1037 - 1042
  • [29] Analyzing the Model of Transformer Windings Under Very Fast Transient Overvoltage
    Liu, Shiming
    Fu, Chuanshun
    Zang, Ying
    Zhang, Shunqin
    Li, Shuai
    Huang, Qiyan
    2018 JOINT IEEE INTERNATIONAL SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY AND 2018 IEEE ASIA-PACIFIC SYMPOSIUM ON ELECTROMAGNETIC COMPATIBILITY (EMC/APEMC), 2018, : 272 - 276
  • [30] Research and design of the 2.5 MV very fast transient overvoltage generator
    Yin, Yu
    Liu, Shi
    Shi, Weidong
    Wang, Shaowu
    Zhang, Lu
    Li, Long
    Zhang, Cuixia
    Zhang, Qiaogen
    Zhao, Wenqiang
    Wu, Ke
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2011, 31 (31): : 48 - 55