Modeling the performance of electronic expansion valves in heat pumps under soft faults

被引:0
|
作者
Llopis-Mengual, Belen [1 ]
Navarro-Peris, Emilio [1 ]
机构
[1] Univ Politecn Valencia UPV, Inst Univ Invest Ingn Energet IUIIE, Camino Vera S-N, Valencia 46022, Spain
关键词
Heat pump; Refrigerant charge; EEV; Liquid line restriction; Fault modeling; Soft fault; MASS-FLOW CHARACTERISTICS; AIR-CONDITIONER; CONDENSATION; CHARGE;
D O I
10.1016/j.rineng.2024.102832
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Heat pumps can have soft faults that cause them to keep operating but not as efficiently as they should. Detecting them is essential for proper maintenance. Nowadays, heat pumps usually include as expansion device electronic expansion valves (EEV), which generally control the superheat (SH) at the outlet of the evaporator. When soft faults occur, such as an undercharge or liquid line restrictions, the EEV opens to continue controlling the SH but becomes fully open at some point. Therefore, its behavior becomes a fixed orifice, and it can no longer continue to control. This study models the performance of the EEV for different conditions in heat pumps under soft faults, and it is validated with an experimental campaign in which the EEV opening is measured at different operating conditions and refrigerant charge levels. The evolution of the main system variables affected by the imposed fault levels of undercharge, overcharge, and liquid line restrictions are also analyzed.
引用
收藏
页数:9
相关论文
共 50 条
  • [1] Optimized transcritical CO2 heat pumps:: Performance comparison of capillary tubes against expansion valves
    Agrawal, Neeraj
    Bhattacharyya, Souuik
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (03): : 388 - 395
  • [2] Soft faults in residential heat pumps: Possibility of evaluation via on-field measurements and related degradation of performance
    Pelella, F.
    Viscito, L.
    Mauro, A. W.
    ENERGY CONVERSION AND MANAGEMENT, 2022, 260
  • [3] Soft faults in residential heat pumps: Possibility of evaluation via on-field measurements and related degradation of performance
    Pelella, F.
    Viscito, L.
    Mauro, A.W.
    Energy Conversion and Management, 2022, 260
  • [4] Generalized effects of faults on normalized performance variables of air conditioners and heat pumps
    Mehrabi, Mehdi
    Yuill, David
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 85 : 409 - 430
  • [5] Performance of heat pumps with direct expansion in vertical ground heat exchangers in heating mode
    De Carli, Michele
    Fiorenzato, Stefano
    Zarrella, Angelo
    ENERGY CONVERSION AND MANAGEMENT, 2015, 95 : 120 - 130
  • [6] Computational modeling and prediction of the performance of air source heat pumps under frost prevention and retardation conditions
    Tang, Jinchen
    Hu, Xuegong
    Herman, Cila
    Gong, Guangcai
    ENERGY AND BUILDINGS, 2020, 224
  • [7] Numerical modeling of heat transfer mechanism in remote sensing bulb of thermal expansion valves
    Alam, Saima
    Gower, Blake
    Mueller, Norbert
    INTERNATIONAL JOURNAL OF THERMAL SCIENCES, 2025, 208
  • [8] FLOW CHARACTERISTICS OF ELECTRONIC EXPANSION VALVES FOR HEAT PUMP SYSTEM USING CARBON DIOXIDE AS A REFRIGERANT
    Kim, Ook Joong
    Choi, Young-Ho
    Yoon, Seok Ho
    PROCEEDINGS OF THE ASME FLUIDS ENGINEERING DIVISION SUMMER CONFERENCE - 2010 - VOL 1, PTS A-C, 2010, : 1041 - 1046
  • [9] Performance study of thermostatic and electronic expansion valves of a water-cooled scroll chiller
    Department of Mechanical Engineering, National University of Singapore, 10 Kent Ridge Crescent, Singapore
    119260, Singapore
    Asian Conf. Refrig. Air Cond., ACRA - Green Breeze Asia: Front. Refrig., Heat Transf. Syst.,
  • [10] Performance degradation of air source heat pumps under faulty conditions
    Mauro, Alfonso William
    Pelella, Francesco
    Viscito, Luca
    CASE STUDIES IN THERMAL ENGINEERING, 2023, 45