Determination of the defrosting duration ratio for defrosting performance evaluation of air source heat pump

被引:0
|
作者
Li, Zhaoyang [1 ]
Wei, Wenzhe [1 ]
Wang, Wei [1 ,2 ]
Sun, Yuying [1 ]
Wang, Shiquan [1 ]
Tang, Rui [1 ]
Lin, Yao [1 ]
Huang, Chengyang [1 ]
Deng, Shiming [3 ]
机构
[1] Beijing Univ Technol, Beijing Key Lab Green Built Environm & Energy Effi, Beijing 100124, Peoples R China
[2] Beijing Inst Petrochem Technol, Sch Safety Engn, Beijing 102627, Peoples R China
[3] Qatar Univ, Dept Mech & Ind Engn, POB 2713, Doha, Qatar
来源
基金
中国国家自然科学基金;
关键词
Air source heat pump; Frosting; Defrosting; Optimal defrosting duration ratio; Characteristic index ( CICO ); SURFACE;
D O I
10.1016/j.jobe.2024.110305
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Defrosting performance evaluation is an important aspect for pre-delivery inspection of air source heat pumps (ASHPs). According to GB/T 25127-2020 and ANSI/AHRI 550/590-2023, defrosting duration ratio (alpha) alpha ) should not exceed 20 % of the frosting-defrosting cycle. This value has remained unchanged for over 20 years. However, with the rapid iteration of defrosting technology, the alpha of new ASHPs has been decreased significantly. Hence, the applicability of this index value deserves to be deliberated. To solve this issue, a method for determining the optimal alpha was proposed firstly. Then, the alpha under different characteristic index ( CICO ) values at 2/1 degrees C and 2/0 degrees C were investigated at the optimal and original defrosting initiating time point ( t opt , t ori ), using twelve ASHPs from nine manufacturers. Results indicates the frosting duration (tf) t f ) is directly proportional to defrosting duration (tdf), t df ), at the same ambient air condition and CICO. . For Unit C, when t f is increased from 30.0 min to 60.0 min and 90.0 min at the CICO of 10.0 x 106, 6 , t df increases from 2.43 min to 3.20 min and 4.03 min at 2/1 degrees C, respectively. No matter at t opt nor t ori , the range of alpha is 1.4%-9.9 %. It is suggested that the 10 % is used as the new index for defrosting performance evaluation of ASHP.
引用
收藏
页数:18
相关论文
共 50 条
  • [31] A visual defrosting control method for air source heat pump system based on machine vision
    Zhao, Han
    Liu, Zihan
    Sang, Yufeng
    Chang, Junzhi
    Zheng, Xuejing
    Jurasz, Jakub
    Zheng, Wandong
    ENERGY, 2024, 302
  • [32] Investigation on the ultrasonic propagation mechanism and its application on air-source heat pump defrosting
    Tan, Haihui
    Xu, Guanghua
    Tao, Tangfei
    Zhang, Sicong
    Luo, Ailing
    APPLIED THERMAL ENGINEERING, 2016, 107 : 479 - 492
  • [33] Experimental study on energy storage air source heat pump system with quick heating and defrosting
    Zhao H.
    Qiu G.
    Yu S.
    Qiu, Guodong (qgd518@163.com), 1600, Science Press (42): : 184 - 190
  • [34] Performance of an air-source heat pump with multi-circuit outdoor coil for continuous heating during defrosting
    Tang, Lan
    Liu, Xi 'an
    He, Shiquan
    Li, Qingjian
    JOURNAL OF BUILDING ENGINEERING, 2024, 85
  • [35] Surface water vaporization model of air source heat pump defrosting based on experimental parameters
    Mechanical and Power Engineering College, Harbin University of Science and Technology, Harbin 150080, China
    不详
    不详
    Shanghai Jiaotong Daxue Xuebao, 2008, 6 (989-992):
  • [36] Experimental study of the characteristic of defrosting for air source heat pump with phase change energy storage
    Dong, Jian-Kai
    Jiang, Yi-Qiang
    Yao, Yang
    Hu, Wen-Ju
    Hunan Daxue Xuebao/Journal of Hunan University Natural Sciences, 2011, 38 (01): : 18 - 22
  • [37] An Experimental Study on the Improvement of Reverse Cycle Defrosting Performances for a Cascade Air Source Heat Pump using Thermal Energy Storage Based Defrosting Method
    Qu, Minglu
    Qin, Ruifeng
    Tang, Yongbo
    Fan, Yanan
    Li, Tianrui
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 818 - 825
  • [38] An experimental investigation on reverse-cycle defrosting performance for an air source heat pump using an electronic expansion valve
    Qu, Minglu
    Xia, Liang
    Deng, Shiming
    Jiang, Yiqiang
    APPLIED ENERGY, 2012, 97 : 327 - 333
  • [39] A data-driven evaluating method on the defrosting effect of the air source heat pump system in Beijing
    Guo, Yanhua
    Shao, Shuangquan
    Geng, Xudong
    Li, Hao
    Wang, Zhichao
    Akkurt, Nevzat
    APPLIED THERMAL ENGINEERING, 2023, 235
  • [40] A modeling study on alleviating uneven defrosting for a vertical three-circuit outdoor coil in an air source heat pump unit during reverse cycle defrosting
    Song Mengjie
    Xia Liang
    Deng Shiming
    APPLIED ENERGY, 2016, 161 : 268 - 278