Sharing of Primary Frequency Response Using LCC-HVDC

被引:0
|
作者
Xue, Ying [1 ]
Chen, Yiping [2 ]
Zheng, Waisheng [3 ]
Tang, Yuan [4 ]
Li, Zhixuan [1 ]
Yang, Conghuan [5 ]
Tang, Wenhu [1 ]
机构
[1] South China Univ Technol, Sch Elect Power Engn, Guangzhou 510641, Peoples R China
[2] China Southern Power Grid, Power Dispatching & Control Ctr, Guangzhou 510663, Peoples R China
[3] China Southern Grid Co Ltd, Strateg Planning Dept, Guangzhou 510663, Peoples R China
[4] Guangdong Power Grid Co Ltd, Hydrogen Energy Res Ctr, Guangzhou Power Supply Bur, Guangzhou 510630, Peoples R China
[5] Guangzhou Maritime Univ, Guangzhou 510725, Peoples R China
基金
中国国家自然科学基金;
关键词
Frequency control; Inverters; Rectifiers; HVDC transmission; Voltage control; Voltage measurement; Frequency response; HVDC; LCC-HVDC;
D O I
10.1109/TPWRD.2024.3415052
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Power systems worldwide are transforming into renewable-dominated ones that require significant grid flexibility. While extensive research has been done on flexibility from the generation or demand side, there is a significant lack of research on studying flexibility from the grid side. Therefore, this paper proposes a primary frequency response sharing strategy using LCC-HVDC for inverter frequency control. Under an inverter frequency event, the proposed method imposes a controlled load change that is proportional to the inverter AC frequency deviation on the rectifier AC network. This in impact activates the primary frequency response from the rectifier side to support the inverter AC frequency (i.e., sharing of primary frequency response). The level of support and the coupled dynamics of rectifier and inverter frequencies are quantified by the developed mathematical model. The model reveals that the inverter load change is affecting the rectifier AC frequency through two cascaded 2(nd) order transfer functions. With the developed model and the desired frequency nadirs at both AC systems, the controller parameters of the proposed method are calculated. This ensures that appropriate level of primary frequency response is shared without jeopardizing the frequency performance of rectifier AC system. The effectiveness of the proposed method is demonstrated using a modified four-generator two-area system. Estimation errors of network inertia and droop constants are discussed.
引用
收藏
页码:2457 / 2469
页数:13
相关论文
共 50 条
  • [21] Tapping Existing LCC-HVdc Systems with Voltage Source Converters
    Suriyaarachchi, D. H. R.
    Karawita, C.
    Mohaddes, M.
    2016 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PESGM), 2016,
  • [22] The strength indexes of the islanded LCC-HVDC sending power system
    Xing, Facai
    Zhou, Yuzhi
    Wang, Shijia
    Xu, Zheng
    INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2019, 29 (04):
  • [23] LCC-HVDC送端电网等值方案研究
    高本锋
    王刚
    刘毅
    刘新元
    胡永强
    郝育黔
    电工技术学报, 2021, 36 (15) : 3250 - 3263+3271
  • [24] Economy Analysis of Flexible LCC-HVDC Systems with Controllable Capacitors
    Chen, Nan
    Zha, Kunpeng
    Qu, Haitao
    Li, Fangling
    Xue, Ying
    Zhang, Xiao-Ping
    CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, 2022, 8 (06): : 1708 - 1719
  • [25] Effects of VSC-HVDC on Receiving-end System Strength of LCC-HVDC
    Xia C.
    Wang Z.
    Zhou B.
    Nie J.
    Hong C.
    Dianwang Jishu/Power System Technology, 2019, 43 (06): : 2031 - 2038
  • [26] An improved prediction method of subsequent commutation failure of an LCC-HVDC considering sequential control response
    Jinxin Ouyang
    Xinyu Pan
    Junjun Ye
    Chao Xiao
    Yanbo Diao
    Qingwu Zhang
    Protection and Control of Modern Power Systems, 2023, 8
  • [27] Fault Detection Using Backward Propagating Traveling Waves for Bipolar LCC-HVDC Lines
    Tiwari, Ravi Shankar
    Gupta, Om Hari
    Sood, Vijay K. K.
    ELECTRIC POWER COMPONENTS AND SYSTEMS, 2022, 50 (9-10) : 516 - 529
  • [28] Harmonic Distortion of LCC-HVDC and VSC-HVDC Link in Eskom's Cahora Bassa HVDC
    Oni, Oluwafemi E.
    Davidson, Innocent E.
    2016 IEEE INTERNATIONAL CONFERENCE ON RENEWABLE ENERGY RESEARCH AND APPLICATIONS (ICRERA), 2016, : 484 - 489
  • [29] An improved prediction method of subsequent commutation failure of an LCC-HVDC considering sequential control response
    Ouyang, Jinxin
    Pan, Xinyu
    Ye, Junjun
    Xiao, Chao
    Diao, Yanbo
    Zhang, Qingwu
    PROTECTION AND CONTROL OF MODERN POWER SYSTEMS, 2023, 8 (01)
  • [30] Response Mechanism of DFIG to Transient Voltage Disturbance Under Commutation Failure of LCC-HVDC System
    Zheng, Zixuan
    Ren, Jie
    Xiao, Xianyong
    Huang, Chunjun
    Wang, Yang
    Xie, Qi
    IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (06) : 2972 - 2979