Transient Stability Enhancement Using Adaptive Neuro-Fuzzy-Based Unified Power Flow Controller

被引:0
|
作者
Alemu, Yechale Amogne [1 ]
Gessesse, Belachew Bantyirga [2 ]
Mossie, Molla Addisu [2 ]
机构
[1] Woldia Univ, Woldia Inst Technol, Sch Elect & Comp Engn, POB 400, Woldia, Ethiopia
[2] Bahir Dar Univ, Bahir Dar Inst Technol BiT, Fac Elect & Comp Engn, POB 26, Bahir Dar, Ethiopia
关键词
FACTs; UPFC; PI Controller; ANFIS; Power system; PSO; STATCOM; TSSC; SYSTEM; IMPROVEMENT; MITIGATION;
D O I
10.1016/j.sciaf.2024.e02195
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
A power system is a complex, non-linear, and dynamic system, with operating parameters that change over time. Because of the complexity of big load lines and faults, high-voltage transmission power systems are usually vulnerable to transient instability concerns, resulting in power losses and increased voltage variation. This issue has the potential to cause catastrophic events such as cascade failure or widespread blackouts. This problem affects Ethiopia's high-voltage transmission power grid in the North-West area. Because of the increased demand for electrical energy, transmission lines' maximum carrying capacity should be enhanced to maintain a secure and uninterrupted power supply to consumers. To address the problem, an adaptive neuro-fuzzybased unified power flow controller (ANFIS-based UPFC) is used for high-voltage transmission lines. This device was chosen as the ideal alternative due to its capacity to rapidly correct reactive power on high-voltage transmission networks. The particle swarm optimization (PSO) algorithm was used to determine the best location for the UPFC. The ANFIS controller receives voltage error and rate of change of voltage error as inputs. 70% of the retrieved data is used for ANFIS training and 30% for ANFIS testing. To show the performance of the proposed controller, several disturbances such as three-phase with ground fault and single-phase with ground fault are used. When a three-phase with ground fault occurs at the mid-point of the Beles to Bahir Dar transmission line, for example, the settling time of rotor angle deviation, rotor speed, rotor speed deviation, and output active power of synchronous generators using ANFIS-based UPFC is reduced by 70.58%, 37.75%, 37.75%, and 43.75%, respectively, compared to a system without UPFC. At peak load, PI-based UPFC and ANFIS-based UPFC reduce active power loss by 51.25% and 71.50%, respectively, compared to a system without UPFC on the Beles to Bahir Dar transmission line. In terms of percentage overshoot and settling time, ANFIS-based UPFC outperforms PI-based UPFC for transient stability enhancement.
引用
收藏
页数:26
相关论文
共 50 条
  • [41] Performance evaluation of unified power flow controller using transient simulation
    Kulkarni, AM
    Padiyar, KR
    [J]. 1997 INTERNATIONAL CONFERENCE ON POWER ELECTRONICS AND DRIVE SYSTEMS, PROCEEDINGS, VOLS 1 AND 2, 1997, : 734 - 739
  • [42] Neuro-fuzzy-based biometric system using speech features
    Shukla, Anupam
    Tiwari, Ritu
    Rathore, Chandra Prakash
    [J]. INTERNATIONAL JOURNAL OF BIOMETRICS, 2010, 2 (04) : 391 - 406
  • [43] An adaptive fuzzy sliding mode controller for reactive power & transient stability management
    Mohanty, Asit
    Viswavandya, Meera
    Ray, Prakash Kumar
    [J]. PROCEEDINGS OF THE 2016 IEEE REGION 10 CONFERENCE (TENCON), 2016, : 3195 - 3199
  • [44] Harmonic Level Minimization Using Neuro-Fuzzy-Based SVPWM
    Ponnapalli, Bhanu
    Natarajan, Pappa
    [J]. IETE JOURNAL OF RESEARCH, 2018, 64 (02) : 247 - 262
  • [45] Optimal control of unified power flow controller (UPFC) to enhance power system transient stability
    Niaki, SAN
    [J]. IRANIAN JOURNAL OF SCIENCE AND TECHNOLOGY, 2003, 27 (B4): : 799 - 806
  • [46] Enhancement of transient stability of multi-machine power systems by using fuzzy-genetic controller
    Senjyu, T
    Miyazato, A
    Uezato, K
    [J]. JOURNAL OF INTELLIGENT & FUZZY SYSTEMS, 2000, 8 (01) : 19 - 26
  • [47] Analysis and design of single-phase power factor corrector with genetic algorithm and adaptive neuro-fuzzy-based sliding mode controller using DC–DC SEPIC
    Subbiah Durgadevi
    Mallapu Gopinath Umamaheswari
    [J]. Neural Computing and Applications, 2019, 31 : 6129 - 6140
  • [48] Development of a fuzzy rule based generalized unified power flow controller
    Singh, J. G.
    Tripathy, P.
    Singh, S. N.
    Srivastava, S. C.
    [J]. EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2009, 19 (05): : 702 - 717
  • [49] Development of adaptive UPFC supplementary fuzzy controller for power system stability enhancement
    Chung, TS
    Yang, XD
    Fang, DZ
    Chung, CY
    [J]. PROCEEDINGS OF THE 2004 IEEE INTERNATIONAL CONFERENCE ON ELECTRIC UTILITY DEREGULATION, RESTRUCTURING AND POWER TECHNOLOGIES, VOLS 1 AND 2, 2004, : 216 - 221
  • [50] Transient Stability Enhancement by DSSC with Fuzzy Supplementary Controller
    Mansour-Khalilian
    Maghsoud-Mokhtari
    Daryoosh-Nazarpour
    Behrouz-Tousi
    [J]. JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2010, 5 (03) : 415 - 422