Seismic Vulnerability Analysis of the High-end Suspended Converter Valve Hall Circuit in the ±800kV Converter Station

被引:0
|
作者
Hu, Jinyu [1 ]
Xie, Qiang [1 ]
机构
[1] Tongji Univ, Coll Civil Engn, Shanghai 200092, Peoples R China
基金
国家重点研发计划; 中国国家自然科学基金;
关键词
High-end suspended converter valve hall circuit; Suspended converter valve; Finite element; Seismic vulnerability; Multiple stripe analysis;
D O I
10.2991/978-94-6463-449-5_82
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Suspended converter valve hall circuit is a crucial subsystem within the UHV converter station. It is characterized by electrical equipment possessing attributes of "high, large, heavy, and flexible," making them prone to seismic-induced damage. In order to evaluate the seismic performance and vulnerability of the equipment within this circuit environment, this study establishes a refined finite element model for the high-end valve hall circuit of a specific 800kV converter station. Through time-history response analysis, the seismic response characteristics and potential failure modes under seismic action are investigated. Utilizing Multiple stripe analysis method, seismic vulnerability curves for each failure mode as well as the overall circuit are obtained. A comparative analysis is conducted between the overall circuit vulnerability curve and the circuit vulnerability curve considering each equipment failure as an independent event. This study serves as a reference for seismic reinforcement of critical equipment in existing converter stations at the circuit level, establishing the groundwork for evaluating the seismic resilience of converter stations. The results indicate that the base frequency of the converter valve tower in the valve hall is relatively low, leading to excessive bottom displacement response under seismic action. Moreover, significant stress responses are observed in the electrical component support structures, post insulators, and 800kV wall bushings within the valve tower layers under seismic action. Failure modes of the high-end valve hall circuit include relative displacement of adjacent converter valve tower bases, exceeding stress limits in electrical component support structures within the layers, as well as exceeding stress limits at the bottom of post insulators and 800kV wall bushings. Furthermore, the failures of each equipment are correlated, and treating equipment failures as independent events would greatly overestimate the vulnerability of the circuit.
引用
收藏
页码:826 / 841
页数:16
相关论文
共 41 条
  • [1] Seismic vulnerability analysis of ±800 kV converter transformer
    Li X.
    Xie Q.
    Zhendong yu Chongji/Journal of Vibration and Shock, 2022, 41 (15): : 244 - 251
  • [2] Cooling System Circuit Analysis of ±800kV DC Power Transmission Converter Valve
    You, Shaohua
    Tan, Qibin
    Wang, Maozhong
    Zong, Luxiang
    PROCEEDINGS OF THE 2015 4TH INTERNATIONAL CONFERENCE ON COMPUTER, MECHATRONICS, CONTROL AND ELECTRONIC ENGINEERING (ICCMCEE 2015), 2015, 37 : 1131 - 1134
  • [3] Seismic Response Analysis on Connected Circuit of the Composite Insulator of ±800 kV Converter Station
    Zhu Z.
    Zhang L.
    Cheng Y.
    Lu Z.
    Liu Z.
    Li S.
    Zhong M.
    Zhang, Lingxin (lingxin_zh@126.com), 2018, Sichuan University (50): : 23 - 30
  • [4] E-field Distribution Analysis on Three Types of Converter Double Valve in 800kV Valve Hall
    Wang, Jialong
    Wu, Hao
    Deng, Zhixiang
    Peng, Zongren
    Liao, Jintao
    2015 IEEE 11TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, 2015, : 692 - 695
  • [5] Calculation Methods of Direct Lightning Shielding in ± 800kV Converter Station
    Luo Jianbin
    HaoYanpeng
    Li Licheng
    Liu Qin
    Mao Changgen
    Han Yongxia
    2011 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2011,
  • [6] ±800kV DC Power Transmission Converter Valve Structure Research
    You, Shaohua
    Tan, Qibin
    Wang, Maozhong
    Zong, Luxiang
    PROCEEDINGS OF THE 2015 4TH INTERNATIONAL CONFERENCE ON COMPUTER, MECHATRONICS, CONTROL AND ELECTRONIC ENGINEERING (ICCMCEE 2015), 2015, 37 : 1127 - 1130
  • [7] Measurement and Calculation of Potential Shifting Current in ±800kV HVDC Converter Station
    Wu, Tian
    Liu, Kai
    Liu, Ting
    Xiao, Bin
    Peng, Yong
    Su, Ziming
    Tang, Pan
    Lei, Xinglie
    2015 5TH INTERNATIONAL CONFERENCE ON ELECTRIC UTILITY DEREGULATION AND RESTRUCTURING AND POWER TECHNOLOGIES (DRPT 2015), 2015, : 1673 - 1678
  • [8] Research on DC Transient Overvolatge and Insulation Coordination of ±800kV Converter Station
    Han Yongxia
    Chen Huixiang
    Lu Yuxin
    Li Licheng
    2011 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2011,
  • [9] Seismic Vulnerability Analysis of UHV Converter Station System
    Liang H.
    Xie Q.
    Dianwang Jishu/Power System Technology, 2022, 46 (02): : 551 - 557
  • [10] Simulation and analysis of resonant overvoltage of ac system at ± 800kV converter station based on EMTS/EMTPE
    Ren Zheng
    Chen Xiaolu
    Gao He
    Zheng Bowen
    Lu Jianqiang
    2018 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2018, : 892 - 896