Seismic Vulnerability Analysis of UHV Converter Station System

被引:0
|
作者
Liang H. [1 ]
Xie Q. [1 ]
机构
[1] College of Civil Engineering, Tongji University, Yangpu District, Shanghai
来源
基金
中国国家自然科学基金;
关键词
Converter station; Seismic vulnerability; Sensitive analysis; UHV;
D O I
10.13335/j.1000-3673.pst.2021.0381
中图分类号
学科分类号
摘要
The converter stations are the essential nodes in an UHV DC transmission system. To evaluate the seismic vulnerability of the UHV converter stations as a whole system, the converter station is divided into several critical loops and a corresponding systematic functional logic model is built up according to the layout and logic relationships of the equipment loops in the converter station. Taking the delivery of the electric power after the earthquake as the system performance evaluation index, the systematic functional state is classified into five levels. Based on the seismic failure probability model of the divided subsystems, the failure probabilities and the seismic vulnerability curves in different functional states of the converter station system under different seismic intensities are obtained via the enumeration method with the failure mode and the impact analysis. And the weak links of the converter station system is identified through the sensitivity analysis of the vulnerability parameters of the divided subsystems. © 2022, Power System Technology Press. All right reserved.
引用
收藏
页码:551 / 557
页数:6
相关论文
共 28 条
  • [1] SCHIFF A J., Northridge earthquake: lifeline performance and post-earthquake response1995, (1995)
  • [2] YU Yongqing, LI Guangfan, LI Peng, Et al., Investigation and analysis of electric equipment damage in Sichuan power grid caused by Wenchuan earthquake, Power System Technology, 32, 11, pp. 5-10, (2008)
  • [3] XIE Q, ZHU R., Damage to electric power grid infrastructure caused by natural disasters in China, IEEE Power and Energy Magazine, 9, 2, pp. 28-36, (2011)
  • [4] EIDINGER J, DAVIS C, TANG A, Et al., M 9. 0 Tohoku earthquake March 11 2011 performance of water and power systems, (2012)
  • [5] LIU Zehong, Innovation practice of ±1100kV UHV DC transmission project grid, Proceedings of the CSEE, 40, 23, pp. 7782-7792, (2020)
  • [6] SHU Y, CHEN W., Research and application of UHV power transmission in China, High Voltage, 3, 1, pp. 1-13, (2018)
  • [7] QIU Ning, CHENG Yongfeng, ZHONG Min, Et al., Progress and prospect in seismic research of 1000kV UHV AC electrical equipment, High Voltage Engineering, 41, 5, pp. 1732-1739, (2015)
  • [8] LONG Rishang, ZHANG Jianghua, MENG Yuang, Et al., Risk assessment method of UHV AC/DC power system in serious disasters, Power System Technology, 41, 9, pp. 2939-2946, (2017)
  • [9] WANG Liming, WANG Chuang, FU Guanjun, Et al., Antiseismic characteristics of composite post insulators for smoothing reactors on UHVDC, High Voltage Engineering, 37, 9, pp. 2081-2088, (2011)