Partially coupled transmission line fault location using single-ended measurements

被引:0
|
作者
Duan, Mengzhao [1 ,2 ]
Ye, Aoshuang [3 ]
Liu, Yu [1 ,2 ]
机构
[1] ShanghaiTech Univ, Sch Informat Sci & Technol, Shanghai 201210, Peoples R China
[2] Minist Educ, Key Lab Control Power Transmiss & Convers SJTU, Shanghai 200240, Peoples R China
[3] State Grid Shanghai Pudong Power Supply Co, Shanghai 200120, Peoples R China
基金
中国国家自然科学基金;
关键词
Fault location; Partially coupled transmission lines; Single -ended measurements; Distributed parameter model; ALGORITHM;
D O I
10.1016/j.epsr.2024.110496
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Accurate fault location technology can not only speed up fault search but also enhance the power supply reliability. This paper introduces a single-ended fault location framework for single line to ground faults, taking into account the effects of partially coupled lines. The proposed framework relies only on local measurements. Within the proposed framework, the two methods proposed in this paper are based on the impedance line model and the fully distributed parameter line model, respectively. The impedance model based fault location method does not require iteration and has no risk of divergence, while the method based on the fully distributed parameter model has higher accuracy. The estimated results of the impedance-based method can be used as the initial values of the solution of the distributed parameter model based method. The proposed methods are validated through a number of testing cases, encompassing various fault locations, resistances, and coupling ratios.
引用
收藏
页数:14
相关论文
共 50 条
  • [31] A New Single-ended Fault Location Method Based on Bergeron Model
    Xin, Jianbo
    Lin, Xiangning
    Bo, Zhiqian
    MATERIALS SCIENCE AND INFORMATION TECHNOLOGY, PTS 1-8, 2012, 433-440 : 2939 - +
  • [32] A new single ended fault location algorithm for combined transmission line considering fault clearing transients without using line parameters
    Niazy, Ismail
    Sadeh, Javad
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 44 (01) : 816 - 823
  • [33] Evaluation of single-ended impedance-based transmission fault location using fixed and variable window phasor estimation approaches
    Reis, R. L. A.
    Lopes, F. V.
    Leite, E. J. S.
    Zat, G.
    Souza, J. V.
    Scheid, A.
    Jahn, T. G.
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 223
  • [34] An improved single-ended correlation-based fault location technique using traveling waves
    Reis, R. L. A.
    Lopes, F., V
    Neves, W. L. A.
    Fernandes Jr, D.
    Ribeiro, C. M. S.
    Cunha, G. A.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 132
  • [35] Modified Single-Ended Fault Location Method for Single-phase-to-Ground Faults in T-Connected Line
    He, Xin
    Zhao, Yiming
    Shi, Shenxing
    2018 2ND IEEE CONFERENCE ON ENERGY INTERNET AND ENERGY SYSTEM INTEGRATION (EI2), 2018,
  • [36] Fault location on a transmission line using synchronized voltage measurements
    Brahma, SM
    Girgis, AA
    IEEE TRANSACTIONS ON POWER DELIVERY, 2004, 19 (04) : 1619 - 1622
  • [37] Single-ended multi-method phasor-based approach for optimized fault location on transmission lines
    Lopes, Felipe, V
    Leite Jr, Eduardo Jorge S.
    Ribeiro, Joao Paulo G.
    Piardi, Artur B.
    Scheid, Allan, V
    Zat, Guilherme
    Espinoza, Renzo G. F.
    ELECTRIC POWER SYSTEMS RESEARCH, 2022, 212
  • [38] Reflected Traveling Wave Based Single-Ended Fault Location in Distribution Networks
    Shi, Yangang
    Zheng, Tao
    Yang, Chang
    ENERGIES, 2020, 13 (15)
  • [39] A single-ended current direction transient protection of UHVDC transmission line
    Chen, Shilong
    Zhang, Jie
    Liu, Hongrui
    Xie, Jiawei
    Hou, Yunchuan
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2016, 31 (02): : 171 - 177
  • [40] Highlight - a recently completed project - An advanced single-ended fault location scheme
    Thomas, DWP