Research on Inversion Model of Winding Hot Spot Temperature of 10-kV Oil-Immersed Three-Dimensional Coiled Core Transformer

被引:0
|
作者
Chen, Qianyi [1 ,2 ]
Chen, Shaonan [1 ]
Huang, Weixiang [1 ,2 ]
Zhang, Wei [1 ,2 ]
Li, Kewen [1 ]
机构
[1] Guangxi Power Grid Co Ltd, Elect Power Res Inst, Nanning 530023, Peoples R China
[2] Guangxi Power Grid Equipment Monitoring & Diag Eng, Nanning 530023, Peoples R China
来源
IEEE ACCESS | 2024年 / 12卷
关键词
Oil insulation; Temperature measurement; Windings; Power transformer insulation; Oils; Mathematical models; Current transformers; Immersion cooling; Power electronics; Oil-immersed transformer; temperature fluid field; streamline extraction; hot spot temperature inversion; power equipment status monitoring;
D O I
10.1109/ACCESS.2023.3305254
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Realizing online monitoring of the hot spot temperature of grid mounted transformer windings is a challenge for the power industry. The heat exchange process between the internal heat source area and the external field area of the transformer is the direct cause of the temperature increase of the transformer shell. In this paper, based on the numerical coupling calculation of temperature - fluid field of 10kV oil immersed solid coiled iron core transformer, the typical heat flow streamline is extracted, and the measurable temperature characteristic points strongly correlated to the winding hot spot temperature are selected in the heat dissipation area of the shell, and the inversion model of the transformer winding hot spot temperature is established. This article verifies the effectiveness of the simulation results and the accuracy of the inversion model through the multi condition temperature rise test of transformer. The maximum error between the calculated steady-state temperature rise of each temperature measurement point in the simulation model and the test value is no more than 3 degrees C, the simulation calculation results are in good agreement with the test results, and the average absolute error of the inversion model winding hot spot temperature inversion is 2.67 %, the maximum temperature difference is less than 3 degrees C. This research provides an effective method for online monitoring of the hot spot temperature of the winding of a 10kV oil-immersed three-dimensional coil iron core transformer, and provides a reference for the state detection of grid mounted transformers.
引用
收藏
页码:97691 / 97700
页数:10
相关论文
共 25 条
  • [21] The Improved Thermal-circuit Model for hot-spot temperature calculation of Oil-immersed Power Transformers
    Wei Ben-gang
    Fu Chen-zhao
    Li Hong-lei
    Li Ke-jun
    Liang Yong-liang
    2016 IEEE INFORMATION TECHNOLOGY, NETWORKING, ELECTRONIC AND AUTOMATION CONTROL CONFERENCE (ITNEC), 2016, : 809 - 813
  • [22] Prediction of transformer average oil temperature and winding hot spot temperature by edge computation based on LSTSVR model
    Zhang L.
    Yang T.
    Li W.
    Liu Z.
    Zeng C.
    1600, Electric Power Automation Equipment Press (40): : 197 - 202
  • [23] Oil-immersed transformer online hot spot temperature monitoring and accurate life lose calculation based on fiber Bragg grating sensor technology
    Zhang, Xin
    Huang, Ronghui
    Huang, Weizhao
    Yao, Shenjing
    Hou, Dan
    Zheng, Min
    2014 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2014,
  • [24] A nonlinear model and viscosity solution for the temperature field of an oil-immersed self-cooled three-phrase transformer
    Guo, Yuzhen
    Feng, Enmin
    NONLINEAR ANALYSIS-THEORY METHODS & APPLICATIONS, 2007, 66 (09) : 2098 - 2107
  • [25] The Research of the Hot Spot Temperature of the Dry-type Transformer Winding Based on the Inversed-heat Conduction Model
    Zhang Xiaoxia
    Wang Yongqiang
    Li Changyuan
    MACHINERY, MATERIALS SCIENCE AND ENERGY ENGINEERING, 2015, : 831 - 839