Oil insulation; Temperature measurement; Windings; Power transformer insulation; Oils; Mathematical models; Current transformers; Immersion cooling; Power electronics; Oil-immersed transformer; temperature fluid field; streamline extraction; hot spot temperature inversion; power equipment status monitoring;
D O I
10.1109/ACCESS.2023.3305254
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Realizing online monitoring of the hot spot temperature of grid mounted transformer windings is a challenge for the power industry. The heat exchange process between the internal heat source area and the external field area of the transformer is the direct cause of the temperature increase of the transformer shell. In this paper, based on the numerical coupling calculation of temperature - fluid field of 10kV oil immersed solid coiled iron core transformer, the typical heat flow streamline is extracted, and the measurable temperature characteristic points strongly correlated to the winding hot spot temperature are selected in the heat dissipation area of the shell, and the inversion model of the transformer winding hot spot temperature is established. This article verifies the effectiveness of the simulation results and the accuracy of the inversion model through the multi condition temperature rise test of transformer. The maximum error between the calculated steady-state temperature rise of each temperature measurement point in the simulation model and the test value is no more than 3 degrees C, the simulation calculation results are in good agreement with the test results, and the average absolute error of the inversion model winding hot spot temperature inversion is 2.67 %, the maximum temperature difference is less than 3 degrees C. This research provides an effective method for online monitoring of the hot spot temperature of the winding of a 10kV oil-immersed three-dimensional coil iron core transformer, and provides a reference for the state detection of grid mounted transformers.
引用
收藏
页码:97691 / 97700
页数:10
相关论文
共 25 条
  • [1] A Method for Hot Spot Temperature Prediction of a 10 kV Oil-Immersed Transformer
    Deng, Yongqing
    Ruan, Jiangjun
    Quan, Yu
    Gong, Ruohan
    Huang, Daochun
    Duan, Cihan
    Xie, Yiming
    IEEE ACCESS, 2019, 7 : 107380 - 107388
  • [2] Influence of insulation paper on the hot spot temperature of oil-immersed transformer winding
    Luo, Chuan
    Zhao, Zhen-Gang
    Wang, Yu-Yuan
    Liang, Ke
    Zhang, Jia-Hong
    Li, Ying-Na
    Li, Chuan
    MODERN PHYSICS LETTERS B, 2021, 35 (28):
  • [3] Establishment and Verification of 10kV Oil Immersed Transformer Winding Hot Spot Temperature Inversion Model Based on Streamline Analysis
    Deng Y.
    Ruan J.
    Dong X.
    Huang D.
    Zhang C.
    Xian R.
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2023, 43 (08): : 3191 - 3203
  • [4] Research on Hot Spot Temperature Calculation and Analysis of Online Monitoring Method of Oil-immersed Power Transformer Winding
    Zhang, Yun
    PROCEEDINGS OF THE 2ND INTERNATIONAL CONFERENCE ON COMPUTER ENGINEERING, INFORMATION SCIENCE & APPLICATION TECHNOLOGY (ICCIA 2017), 2017, 74 : 692 - 695
  • [5] Research on Overload Capability of Oil-immersed Distribution Transformer Based on Hot Spot Temperature Model
    Wang, Haifei
    Xue, Manyu
    Wang, Tingkang
    Hou, Yuning
    Chen, Jianchun
    Sun, Jianming
    2019 22ND INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS (ICEMS 2019), 2019, : 4478 - 4482
  • [6] Research on the Relationship between Hot Spot Transient Temperature Rise and Ambient Temperature of Oil-immersed Transformer
    Li, Chenlong
    Wang, Zhaoxin
    Fan, Lixin
    Wang, Yongqiang
    Chu, Haijun
    PROCEEDINGS OF 2018 IEEE 4TH INFORMATION TECHNOLOGY AND MECHATRONICS ENGINEERING CONFERENCE (ITOEC 2018), 2018, : 782 - 786
  • [7] 3D modeling of winding hot spot temperature in oil-immersed transformers
    Reza Kebriti
    S. M. Hassan Hossieni
    Electrical Engineering, 2022, 104 : 3325 - 3338
  • [8] 3D modeling of winding hot spot temperature in oil-immersed transformers
    Kebriti, Reza
    Hossieni, S. M. Hassan
    ELECTRICAL ENGINEERING, 2022, 104 (05) : 3325 - 3338
  • [9] Dynamic Inversion Method of Hot Spot Temperature of Oil-immersed Transformer Based on Combination of Multiphysics Simulation and Neural Network Algorithm
    Ni Z.
    Sheng G.
    Zhang L.
    Wang F.
    Gaodianya Jishu/High Voltage Engineering, 2023, 49 (06): : 2466 - 2477
  • [10] Application of Kalman filter to hot-spot temperature monitoring in oil-immersed power transformer
    Chen, Weigen
    Su, Xiaoping
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2013, 8 (04) : 322 - 327