Research on identification method of abnormal grounding circulating current in single-core AC submarine cable

被引:1
|
作者
Yang, Yuxin [1 ,2 ]
Zhu, Yongli [1 ]
Wang, Jinsong [2 ]
Li, Yan [1 ]
机构
[1] North China Elect Power Univ, Dept Elect Engn, Baoding 071003, Hebei, Peoples R China
[2] China Datang Corp Sci & Technol Res Inst, North China Branch, Inst Elect Technol, Beijing, Peoples R China
关键词
submarine cable; single-core; identification method; fault location; circulating current; POWER-CABLES; LOSSES;
D O I
10.1049/gtd2.13190
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The grounding circulation current of the sheath and armour of single-core AC submarine cables is high during operation, which can easily cause insulation damage and faults. Traditional methods that only monitor the amplitude of grounding circulation current make it difficult to detect defects in the cables, so further research is needed on the mathematical mechanism and detection methods of grounding circulation current. A mathematical model for the capacitance and impedance coupling of a single-core submarine cable was established, and the influence of factors such as active power, length of armour stripping section, armour resistivity, armour magnetic permeability and grounding resistance on the grounding circulation current was analysed. A method for identifying abnormal grounding circulation current of submarine cables based on the combination of amplitude and phase was proposed. The grounding circulation current of the sheath and armour of single-core AC submarine cables is high during operation, which can easily cause insulation damage and faults. Traditional methods that only monitor the amplitude of grounding circulation current make it difficult to detect defects in the cables, so further research is needed on the mathematical mechanism and detection methods of grounding circulation current. A mathematical model for the capacitance and impedance coupling of a single-core submarine cable was established, and the influence of factors such as active power, length of armour stripping section, armour resistivity, armour magnetic permeability and grounding resistance on the grounding circulation current was analysed. A method for identifying abnormal grounding circulation current of submarine cables based on the combination of amplitude and phase was proposed. image
引用
收藏
页码:2144 / 2154
页数:11
相关论文
共 33 条
  • [31] Research on a Current Reconstruction Method of Multi-Core Cable Based on Surface Magnetic Field Measurements
    Luo, Ruixi
    Qin, Yuyi
    Zhou, Yifei
    Li, Fuchao
    Wang, Ruihan
    PROGRESS IN ELECTROMAGNETICS RESEARCH M, 2024, 127 : 31 - 39
  • [32] Research on an Equivalent Heat Source Model of the AC Arc in the Short Gap of a Copper-Core Cable and a Fire Risk Assessment Method
    Li, Yu
    Zhang, Rencheng
    Yang, Kai
    Qi, Yufan
    SENSORS, 2024, 24 (05)