Research on identification method of abnormal grounding circulating current in single-core AC submarine cable

被引:1
|
作者
Yang, Yuxin [1 ,2 ]
Zhu, Yongli [1 ]
Wang, Jinsong [2 ]
Li, Yan [1 ]
机构
[1] North China Elect Power Univ, Dept Elect Engn, Baoding 071003, Hebei, Peoples R China
[2] China Datang Corp Sci & Technol Res Inst, North China Branch, Inst Elect Technol, Beijing, Peoples R China
关键词
submarine cable; single-core; identification method; fault location; circulating current; POWER-CABLES; LOSSES;
D O I
10.1049/gtd2.13190
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The grounding circulation current of the sheath and armour of single-core AC submarine cables is high during operation, which can easily cause insulation damage and faults. Traditional methods that only monitor the amplitude of grounding circulation current make it difficult to detect defects in the cables, so further research is needed on the mathematical mechanism and detection methods of grounding circulation current. A mathematical model for the capacitance and impedance coupling of a single-core submarine cable was established, and the influence of factors such as active power, length of armour stripping section, armour resistivity, armour magnetic permeability and grounding resistance on the grounding circulation current was analysed. A method for identifying abnormal grounding circulation current of submarine cables based on the combination of amplitude and phase was proposed. The grounding circulation current of the sheath and armour of single-core AC submarine cables is high during operation, which can easily cause insulation damage and faults. Traditional methods that only monitor the amplitude of grounding circulation current make it difficult to detect defects in the cables, so further research is needed on the mathematical mechanism and detection methods of grounding circulation current. A mathematical model for the capacitance and impedance coupling of a single-core submarine cable was established, and the influence of factors such as active power, length of armour stripping section, armour resistivity, armour magnetic permeability and grounding resistance on the grounding circulation current was analysed. A method for identifying abnormal grounding circulation current of submarine cables based on the combination of amplitude and phase was proposed. image
引用
收藏
页码:2144 / 2154
页数:11
相关论文
共 33 条
  • [1] Characteristic Analysis of the Outer Sheath Circulating Current in a Single-Core AC Submarine Cable System
    Li, Peng
    Guo, Pengcheng
    SYMMETRY-BASEL, 2022, 14 (06):
  • [2] Research on shielding overvoltage of single-core cable
    Niu, H. Q.
    Wang, X. B.
    Shi, Y. X.
    Zhang, Y.
    2007 CONFERENCE PROCEEDINGS IPEC, VOLS 1-3, 2007, : 1317 - +
  • [3] Circulating current method for the on-line monitoring of the multipoint earthing on the metal sheath of the single-core XLPE cable
    Chen, Chuangting
    Zhang, Guosheng
    Zhou, Zhicheng
    Zhang, Dandan
    Chen, Junwu
    He, Junjia
    Wang, Yan
    Li, Zhengying
    Gaodianya Jishu/High Voltage Engineering, 2002, 28 (07):
  • [4] Study on the ampacity of single-core submarine power cable with return conductor
    Fan Youbing
    Liu Songhua
    Li Te
    Deng Xianbo
    2019 INTERNATIONAL CONFERENCE ON ADVANCED ELECTRONIC MATERIALS, COMPUTERS AND MATERIALS ENGINEERING (AEMCME 2019), 2019, 563
  • [5] Development of optical fibers incorporated single-core submarine power cable
    Ogata, Sciichi
    Fujii, Koichiro
    Nishino, Isao
    Hata, Ryosuke
    Yoshikawa, Noriyaso
    Hirose, Masayuki
    Koga, Hisao
    Tanaka, Shigero
    Osaka, Keiji
    Sumitomo Electric Technical Review, 1994, (37):
  • [6] Calculation of current rate in single-core cables with circulating current
    Jia, X.
    Cao, X.L.
    Yu, M.
    Gaodianya Jishu/High Voltage Engineering, 2001, 27 (01):
  • [7] Calculation of AC Resistance for Stranded Single-Core Power Cable Conductors
    Dai, Dong
    Zhang, Xiaohui
    Wang, Juanjuan
    IEEE TRANSACTIONS ON MAGNETICS, 2014, 50 (11)
  • [8] Analysis of the Ampacity Characteristic of Single-Core AC Cable Laid in Water
    Ding Shuchun
    Jian Ganyang
    Liu Gang
    Lei Chenghua
    2011 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2011,
  • [9] Study of ampacity of single-core cable based on iterative method
    Niu, Haiqing
    Wang, Xiaobing
    Zhang, Yao
    Gaodianya Jishu/High Voltage Engineering, 2006, 32 (11): : 41 - 44
  • [10] Parameter Analysis and Research on Sheath Lightning Overvoltage of Single-core Cable
    Niu, Haiqing
    Zhou, Xin
    Zhang, Yao
    Wang, Xiaobing
    Shi, Yinxia
    Xu, Yuxiang
    2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 3497 - +