Experimental and Numerical Study on Early-Warning Approach for Fire-Induced Collapse of Steel Portal Frame Based on Rotational Angles

被引:1
|
作者
Qi, Hong-Hui [1 ]
Jiang, Yaqiang [2 ,3 ,4 ]
Hou, Jing [1 ]
Lou, Guo-Biao [1 ,3 ,5 ]
Zhong, Bo [2 ,3 ,4 ]
Zhang, Zejiang [2 ,3 ,4 ]
He, Qinli [2 ]
机构
[1] Tongji Univ, Coll Civil Engn, Shanghai 200092, Peoples R China
[2] Minist Emergency Management, Sichuan Fire Res Inst, Chengdu 610036, Peoples R China
[3] Minist Emergency Management, Key Lab Fire Protect & Retardant Technol, Chengdu 610036, Peoples R China
[4] Natl Engn Res Ctr Fire & Emergency Rescue, Chengdu 610036, Peoples R China
[5] State Key Lab Disaster Reduct Civil Engn, Shanghai 200092, Peoples R China
基金
中国国家自然科学基金;
关键词
Early warning; Steel portal frame; Collapse; Fire; Rotation; BEHAVIOR;
D O I
10.1007/s10694-024-01645-2
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The existing early-warning methods primarily rely on detecting structural displacements which are often challenging to measure accurately in real fire scenarios. To develop innovative early-warning strategies, this paper experimentally and numerically investigates the fire-induced collapse of an 8 m x 6 m steel portal frame assembly. Detailed thermo-structural responses of the frame were measured and presented, including the displacements and rotations. The results revealed that the vertical mid-span displacement and horizontal displacement at the rafter end are key to developing an effective early-warning system. Structural rotations seem sensitive to structural deformation and emerges as a valuable safety indicator for structural systems. Furthermore, parametric analyses were carried out in order to investigate the effect of load ratio, fire protection and heating curve on key parameters of the structure subjected to fires. It is discovered that the increased load ratio can reduce the peak value of vertical displacement at the mid-span of the rafter. A rotational angle of 6 degrees in the steel beams is optimal for predicting the collapse of steel portal frames in fire conditions. Based on the parametric studies, an innovative early-warning approach using rotational angles is proposed and validated against the test frame, demonstrating significant applicability and reliability. The rotation-based early-warning approach works in two distinct stages, being activated respectively by the maximum and zero rotational angles at the end of rafter. The early-time ratios for the respective warning stages are 0.65 and 0.88. For better precision and practical reliability, it is further recommended to combine the rotation-based and displacement-based approaches for the on-site early-warning of fire-induced collapse of portal frames.
引用
收藏
页码:947 / 974
页数:28
相关论文
共 36 条
  • [1] Early-warning approach for fire-induced collapse of steel portal frame based on overall deformation
    Qi, Hong-Hui
    Lou, Guo-Biao
    Pang, Yansong
    Li, Guo-Qiang
    JOURNAL OF BUILDING ENGINEERING, 2025, 101
  • [2] Early-warning methods for fire-induced collapse of single span steel portal frames
    Ji, Wei
    Li, Guo-Qiang
    Lou, Guo-Biao
    JOURNAL OF CONSTRUCTIONAL STEEL RESEARCH, 2022, 190
  • [3] Synchronous Displacement Acquisition Approach for Early Warning of Fire-induced Collapse of Steel Portal Frames
    Ji, Wei
    Zhu, Shaojun
    Li, Guo-Qiang
    Chen, Bin
    FIRE TECHNOLOGY, 2023, 59 (04) : 1613 - 1645
  • [4] Synchronous Displacement Acquisition Approach for Early Warning of Fire-induced Collapse of Steel Portal Frames
    Wei Ji
    Shaojun Zhu
    Guo-Qiang Li
    Bin Chen
    Fire Technology, 2023, 59 : 1613 - 1645
  • [5] Approach for early-warning collapse of double-span steel portal frames induced by fire
    Ji, Wei
    Zhu, Shaojun
    Li, Guo-Qiang
    Lou, Guobiao
    Jiang, Shouchao
    FIRE SAFETY JOURNAL, 2022, 131
  • [6] Experimental and numerical study on fire-induced collapse of double-span steel portal frames
    Ji, Wei
    Li, Guo-Qiang
    Wang, Yao
    Li, Jinyu
    Zhu, Shaojun
    Yang, Xiaolin
    Chen, Bin
    Chen, Nan
    Chen, Peng
    FIRE SAFETY JOURNAL, 2024, 143
  • [7] Early-warning method for fire-induced collapse of planar triangle and Warren trusses
    Li J.
    Li G.
    Zhu S.
    Jianzhu Jiegou Xuebao/Journal of Building Structures, 2024, 45 (07): : 131 - 142
  • [8] Experimental and numerical study on fire-induced collapse of unprotected steel framed structures
    Qi, Hong-Hui
    Hou, Jing
    Lou, Guo-Biao
    Jiang, Yaqiang
    Zhong, Bo
    Li, Guo-Qiang
    JOURNAL OF CONSTRUCTIONAL STEEL RESEARCH, 2024, 218
  • [9] An approach for early-warning collapse of planar steel trapezoid trusses exposed to fire
    Li, Guo-Qiang
    Li, Jinyu
    Zhu, Shaojun
    FIRE SAFETY JOURNAL, 2023, 137
  • [10] Research on reliability of early-warning methods for collapse prediction of steel portal frames under fire
    Ji W.
    Li G.
    Lou G.
    Jianzhu Jiegou Xuebao/Journal of Building Structures, 2023, 44 (02): : 154 - 164