Analysis of the operation of air-cooled chillers with variable-speed fans for advanced energy-saving-oriented control strategies

被引:2
|
作者
Catrini, Pietro [1 ]
La Villetta, M. [1 ]
Kumar, Dhirendran Munith [2 ]
Morale, Massimo [1 ]
Piacentino, Antonio [1 ]
机构
[1] Univ Palermo, Dept Engn, Viale Sci, Palermo, Italy
[2] Univ South Pacific, Sch Informat Technol Engn Math & Phys, Discipline Elect & Elect Engn, Laucala Campus, Suva, Fiji
关键词
Air conditioning; Energy savings; Chillers; Energy efficiency ratio; Variable-speed compressor; Variable-speed fans; CENTRIFUGAL CHILLERS; PERFORMANCE ANALYSIS; HEAT-PUMP; SYSTEM; REFRIGERANTS; DESIGN;
D O I
10.1016/j.apenergy.2024.123393
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Air-cooled chillers are extensively employed to meet cooling demand in commercial and tertiary sectors. To enhance their performance during part-load operation, variable -speed drives have been integrated into compressors and condenser fans. In existing systems, condenser fans are either operated at a fixed speed or modulated to maintain a predetermined condensing pressure or temperature difference between the refrigerant and outdoor air. In the search for increased efficiency, it is worth investigating innovative control strategies aimed at minimizing energy consumption. A preliminary mapping of chiller performance at different fan speeds, loads, and operating conditions is required to achieve this goal. In this respect, this paper investigates the operation of air-cooled chillers equipped with variable -speed condenser fans, both in the case of constant- and variable -speed compressors. An ad hoc matrix test is adopted to cover appropriate ranges conditions, in terms of load and outdoor air temperatures. Performance maps are developed for a 50-kW c chiller using a 1-D simulator. As the main findings, it may be stated that (i) in the case of the variable -speed chiller, the energy efficiency ratio increases almost linearly with fan speed, resulting in an 8.8% increase when increasing the speed from the nominal to the maximum; (ii) in the case of constant-speed chillers, the system exhibits a different behavior with the cooling capacity and the energy efficiency ratio increasing with the fan speed between 380 and 980 rpm and then decreasing (slightly or sharply, at full and part load respectively) with fan speed between 980 and 1280 rpm, and a percentage increase of EER in the range 7.8 -45% is observed. Also, the sensitivity of such results to the system design is investigated, analyzing a chiller equipped with a larger condenser that resulted in achieving minimum energy consumption at an optimal 980 rpm fan speed. Finally, for a constant-speed chiller serving an office building in the Mediterranean, the proposed fan control strategy could yield an electricity saving of up to 12.1% compared to the base case, confirming the potential for energy savings through optimized and system-tailored management of condenser fan speed.
引用
收藏
页数:15
相关论文
共 37 条
  • [1] Advanced modeling and energy-saving-oriented assessment of control strategies for air-cooled chillers in space cooling applications
    Kumar, Dhirendran Munith
    Catrini, Pietro
    Piacentino, Antonio
    Cirrincione, Maurizio
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2023, 291
  • [2] Part load performance of air-cooled centrifugal chillers with variable speed condenser fan control
    Yu, F. W.
    Chan, K. T.
    [J]. BUILDING AND ENVIRONMENT, 2007, 42 (11) : 3816 - 3829
  • [3] Advanced control of condensing temperature for enhancing the operating efficiency of air-cooled chillers
    Yu, FW
    Chan, KT
    [J]. BUILDING AND ENVIRONMENT, 2005, 40 (06) : 727 - 737
  • [4] An analysis on the energy efficiency of air-cooled chillers with water mist system
    Yang, Jia
    Chan, K. T.
    Wu, Xiangsheng
    Yu, F. W.
    Yang, Xiaofeng
    [J]. ENERGY AND BUILDINGS, 2012, 55 : 273 - 284
  • [5] Modelling of the coefficient of performance of an air-cooled screw chiller with variable speed condenser fans
    Yu, FW
    Chan, KT
    [J]. BUILDING AND ENVIRONMENT, 2006, 41 (04) : 407 - 417
  • [6] Energy saving of fans in air-cooled server via deep reinforcement learning algorithm
    Chu, Wen-Xiao
    Lien, Yun-Hsuan
    Huang, Kuei-Ru
    Wang, Chi-Chuan
    [J]. ENERGY REPORTS, 2021, 7 : 3437 - 3448
  • [7] On energy-saving-oriented high-speed train tracking control scheme
    Jia, Baotong
    Meng, Xuelei
    Jia, Fei
    Ma, Yangyang
    Ren, Yuanyuan
    [J]. Journal of Railway Science and Engineering, 2021, 18 (08) : 1986 - 1996
  • [8] Advanced control of heat rejection airflow for improving the coefficient of performance of air-cooled chillers
    Yu, FW
    Chan, KT
    [J]. APPLIED THERMAL ENGINEERING, 2006, 26 (01) : 97 - 110
  • [9] Controlling cleanroom fans with variable-speed drives saves energy, quiets operation
    Olsson, C
    [J]. I&CS-INSTRUMENTATION & CONTROL SYSTEMS, 1997, 70 (07): : 39 - 42
  • [10] Energy saving and performance analysis of air-cooled photovoltaic panels
    Hussam, Wisam K.
    Khlefat, Ali M.
    Sheard, Gregory J.
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2022, 46 (04) : 4825 - 4834