Experimental study of two-stage parallel desiccant coated heat pump system based on multi-objectives

被引:0
|
作者
Zou, Qihong [1 ]
Li, Qian [1 ]
Ge, Tianshu [1 ]
机构
[1] Institute of Refrigeration and Cryogenics, Shanghai Jiao Tong University, Shanghai,200240, China
来源
关键词
Coefficient of performance - Driers (materials) - Heat pump systems - Pumps;
D O I
10.11949/0438-1157.20221521
中图分类号
学科分类号
摘要
A novel two-stage parallel desiccant coated heat pump system is proposed, the system performance is experimentally studied under air typical conditions. The experiments show that the system can effectively solve the problem of insufficient handling capacity of the sensible heat load of the solid desiccant coated heat pump(SDHP), the sensible and latent heat load can be flexibly deployed in different ratio: it can provide 19.0℃ and 8.81 g/kg of air supply in the comfort zone under typical air conditions, the average COP reached 3.92 under the condensing temperature of 50℃. The COP risen from 3.39 to 5.81 when the condensing temperature changed from 55℃ to 35℃, the sensible heat load ratio is always maintained above 16: 1. The latent load ratio of the system in different environments can reach 7%—60%, which can meet the requirements of temperature and humidity decoupling in most air supply conditions. © 2023 Chemical Industry Press. All rights reserved.
引用
收藏
页码:265 / 271
相关论文
共 50 条
  • [1] Experimental study on a two-stage rotary desiccant cooling system
    Ge, T. S.
    Li, Y.
    Wang, R. Z.
    Dai, Y. J.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2009, 32 (03): : 498 - 508
  • [2] Experimental investigation on a novel heat pump system based on desiccant coated heat exchangers
    Hua, L. J.
    Jiang, Y.
    Ge, T. S.
    Wang, R. Z.
    [J]. ENERGY, 2018, 142 : 96 - 107
  • [3] EXPERIMENTAL STUDY ON A TWO-STAGE LIQUID DESICCANT DEHUMIDIFICATION SYSTEM USING DUAL DESICCANT SOLUTIONS
    Xiong, Z. Q.
    Wang, R. Z.
    Dai, Y. J.
    [J]. HEAT TRANSFER RESEARCH, 2015, 46 (04) : 383 - 397
  • [4] Application of Heat Pump-driven Two-stage Desiccant Wheel System in Office Buildings
    Tu, Rang
    Liu, Xiaohua
    Zhang, Tao
    Jiang, Yi
    [J]. ASHRAE TRANSACTIONS 2014, VOL 120, PT 1, 2014, 120
  • [5] Performance study of a heat pump driven and hollow fiber membrane-based two-stage liquid desiccant air dehumidification system
    Zhang, Ning
    Yin, Shao-You
    Zhang, Li-Zhi
    [J]. APPLIED ENERGY, 2016, 179 : 727 - 737
  • [6] Performance Analysis of Two-Stage Solid Desiccant Densely Coated Heat Exchangers
    Li, Kun-Ying
    Luo, Win-Jet
    Tsai, Bo-Yi
    Kuan, Yean-Der
    [J]. SUSTAINABILITY, 2020, 12 (18)
  • [7] Heat pump combined with single-stage or two-stage desiccant wheel system? A comparative study on different humidity requirement buildings
    Tian, Shaochen
    Su, Xing
    Geng, Yining
    Li, He
    Liang, Yaowen
    Di, Yanqiang
    [J]. Energy Conversion and Management, 2022, 255
  • [8] Heat pump combined with single-stage or two-stage desiccant wheel system? A comparative study on different humidity requirement buildings
    Tian, Shaochen
    Su, Xing
    Geng, Yining
    Li, He
    Liang, Yaowen
    Di, Yanqiang
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2022, 255
  • [9] Theoretical analysis and case study on solar driven two-stage rotary desiccant cooling system combined with geothermal heat pump
    Dai, Yanjun
    Li, Xian
    Wang, Ruzhu
    [J]. INTERNATIONAL CONFERENCE ON SOLAR HEATING AND COOLING FOR BUILDINGS AND INDUSTRY, SHC 2014, 2015, 70 : 418 - 426
  • [10] Two-stage high temperature hybrid heat pump with parallel heat sinks
    Ellingsen, Oyvind Mortveit
    Kvalsvik, Karoline Husevag
    Bantle, Michael
    [J]. 13TH IIR GUSTAV LORENTZEN CONFERENCE ON NATURAL REFRIGERANTS: NATURAL REFRIGERANT SOLUTIONS FOR WARM CLIMATE COUNTRIES, 2018, : 773 - 781