Numerical characterization of heat transfer in closed-loop vertical ground heat exchanger

被引:0
|
作者
Chulho LEE [1 ]
Hujeong GIL [2 ]
Hangseok CHOI [1 ]
ShinHyung KANG [3 ]
机构
[1] School of Civil,Environmental and Architectural Engineering,Korea University,-Ga,Anam-Dong,Seongbuk-Gu,Seoul -,Republic of Korea
[2] Pyungsan SI Co,Ltd,- Seocho-Dong,Seocho-Gu,Seoul -,Republic of Korea
[3] Department of Mechanical Engineering,Konyang University,,Deahak-Ro,Nonsan,Chungnam -,Republic of
关键词
D O I
暂无
中图分类号
TB657.5 [热交换及其设备];
学科分类号
摘要
A series of numerical analyses has been performed on the characteristics of heat transfer in a closed-loop vertical ground heat exchanger(U-loop).A 2-D finite element analysis was conducted to evaluate the temperature distribution over the cross section of the U-loop system involving high-density polyethylene(HDPE) pipe/grout/soil to compare the sectional efficiency between the conventional U-loop and a new latticed HDPE pipe system,which is equipped with a thermally insulating lattice in order to reduce thermal interference between the inlet and outlet pipes.In addition,a 3-D finite volume analysis(FLUENT) was adopted to simulate the operation of the closed-loop vertical ground heat exchanger with the consideration of the effect of a distance between the inlet and outlet pipes,grout's thermal properties,the effectiveness of the latticed HDPE pipe system,and the rate of circulation pump.It was observed that the thermal interference between the two strands of U-loop is of importance in enhancing efficiency of the ground heat exchanger.Consequently,it is recommended to modify the configuration of the conventional U-loop system by equipping the thermally insulating lattice between the two pipe strands.
引用
收藏
页码:111 / 116
页数:6
相关论文
共 50 条
  • [1] Numerical characterization of heat transfer in closed-loop vertical ground heat exchanger
    Lee, Chulho
    Gil, Hujeong
    Choi, Hangseok
    Kang, Shin-Hyung
    SCIENCE CHINA-TECHNOLOGICAL SCIENCES, 2010, 53 (01) : 111 - 116
  • [2] Numerical characterization of heat transfer in closed-loop vertical ground heat exchanger
    Chulho LEE
    Hujeong GIL
    Hangseok CHOI
    Shin-Hyung KANG
    Science China(Technological Sciences), 2010, 53 (01) : 111 - 116
  • [3] Numerical characterization of heat transfer in closed-loop vertical ground heat exchanger
    Chulho Lee
    Hujeong Gil
    Hangseok Choi
    Shin-Hyung Kang
    Science in China Series E: Technological Sciences, 2010, 53 : 111 - 116
  • [4] Numerical simulation for thermal response test performance in closed-loop vertical ground heat exchanger
    CHOI Jong Min
    LEE Chulho
    PARK Moonseo
    KANG Shin-Hyung
    CHOI Hangseok
    Science China(Technological Sciences), 2011, (07) : 1668 - 1673
  • [5] Numerical simulation for thermal response test performance in closed-loop vertical ground heat exchanger
    Jong Min Choi
    Chulho Lee
    Moonseo Park
    Shin-Hyung Kang
    Hangseok Choi
    Science China Technological Sciences, 2011, 54 : 1668 - 1673
  • [6] Numerical simulation for thermal response test performance in closed-loop vertical ground heat exchanger
    CHOI Jong Min
    LEE Chulho
    PARK Moonseo
    KANG ShinHyung
    CHOI Hangseok
    Science China(Technological Sciences), 2011, 54 (07) : 1668 - 1673
  • [7] Numerical simulation for thermal response test performance in closed-loop vertical ground heat exchanger
    Choi, Jong Min
    Lee, Chulho
    Park, Moonseo
    Kang, Shin-Hyung
    Choi, Hangseok
    SCIENCE CHINA-TECHNOLOGICAL SCIENCES, 2011, 54 (07) : 1668 - 1673
  • [8] In-Situ Thermal Response Test for Closed-Loop Vertical Ground Heat Exchanger in Shanghai, China
    Chen, Shuai
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [10] Numerical heat transfer simulations of a vertical batch furnace under closed-loop temperature control
    Wilson, GJ
    McHugh, PR
    Weaver, RA
    PROCEEDINGS OF THE SECOND INTERNATIONAL SYMPOSIUM ON PROCESS CONTROL, DIAGNOSTICS, AND MODELING IN SEMICONDUCTOR MANUFACTURING, 1997, 97 (09): : 110 - 117