DESIGN STUDIES FOR THE MEAD-PHOENIX 500 KV AC TRANSMISSION PROJECT

被引:6
|
作者
THALLAM, RS
LUNDQUIST, TG
ATMURI, SR
SELIN, DA
机构
[1] TESHMONT CONSULTANTS INC,WINNIPEG,MB,CANADA
[2] ARIZONA PUBL SERV CO,PHOENIX,AZ
关键词
SERIES COMPENSATION; PHASE SHIFTING TRANSFORMER; LINE ENERGIZATION; BREAKER TRV; REACTOR SWITCHING;
D O I
10.1109/61.473369
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The Mead-Phoenix 500 kV ac line is 243 miles long and runs parallel to the existing Mead-Liberty 345 kV line. This line is planned for 70% series and 70% shunt compensation; it also incorporates the first application of a 500 kV phase shifting transformer that enables a 1300 MW transmission capacity. This paper presents the design studies that were undertaken in arriving at the equipment ratings and insulation levels that lead to the equipment specifications. The shunt reactor switching requirements utilizing MOV across the breaker,line switching with line connected arresters and the breaker transient recovery voltage are also dealt with in the paper.
引用
收藏
页码:1862 / 1874
页数:13
相关论文
共 50 条
  • [1] Control design for SVC's on the Mead-Adelanto and Mead-Phoenix transmission project
    Larsen, EV
    Clark, K
    Beshir, MJ
    Bhuiyan, M
    Braun, K
    Hill, AT
    Piwko, RJ
    Hromozi, FJ
    IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (03) : 1498 - 1506
  • [2] APPLICATION OF STATIC VAR COMPENSATORS FOR THE DYNAMIC PERFORMANCE OF THE MEAD-ADELANTO AND MEAD-PHOENIX TRANSMISSION PROJECTS
    LEE, RL
    BESHIR, MJ
    FINLEY, AT
    HAYES, DR
    HSU, JC
    PETERSON, HR
    DESHAZO, GL
    GERLACH, DW
    IEEE TRANSACTIONS ON POWER DELIVERY, 1995, 10 (01) : 459 - 466
  • [3] Studies on metallurgical contamination accumulation characteristics on ceramic insulator of 500 kV AC transmission line
    Lan, Lei
    Mu, Lin
    Yuan, Xiaoqing
    Yan, Jing
    Wang, Yu
    Wang, Wei
    Shen, Yang
    Hao, Lu
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2019, 13 (05) : 722 - 728
  • [4] AC 500kV Substation Design in China
    Fang Jing
    Li Baojin
    Ding Shunan(Transmission and Substation Department
    Electricity, 1999, (01) : 42 - 45
  • [7] Study on lightning performance of 1000 kV AC transmission project
    Wuhan High Voltage Research Institute of SGCC, Wuhan 430074, China
    Gaodianya Jishu, 2006, 12 (40-44):
  • [9] Design and Testing of 500kV Double Circuit Monopoles for the Heartland Transmission Project in Edmonton, Alberta
    Kumar, Kishor
    Dwyer, Jason
    ELECTRICAL TRANSMISSION AND SUBSTATION STRUCTURES 2015: TECHNICAL CHALLENGES AND INNOVATIVE SOLUTIONS IN GRID MODERNIZATION, 2015, : 337 - 350
  • [10] Shanghai 500-kV Jing’an transmission & substation project completed
    Liu Chunsheng
    Electricity, 2010, 21 (02) : 3 - 3