DESIGN STUDIES FOR THE MEAD-PHOENIX 500 KV AC TRANSMISSION PROJECT

被引:6
|
作者
THALLAM, RS
LUNDQUIST, TG
ATMURI, SR
SELIN, DA
机构
[1] TESHMONT CONSULTANTS INC,WINNIPEG,MB,CANADA
[2] ARIZONA PUBL SERV CO,PHOENIX,AZ
关键词
SERIES COMPENSATION; PHASE SHIFTING TRANSFORMER; LINE ENERGIZATION; BREAKER TRV; REACTOR SWITCHING;
D O I
10.1109/61.473369
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The Mead-Phoenix 500 kV ac line is 243 miles long and runs parallel to the existing Mead-Liberty 345 kV line. This line is planned for 70% series and 70% shunt compensation; it also incorporates the first application of a 500 kV phase shifting transformer that enables a 1300 MW transmission capacity. This paper presents the design studies that were undertaken in arriving at the equipment ratings and insulation levels that lead to the equipment specifications. The shunt reactor switching requirements utilizing MOV across the breaker,line switching with line connected arresters and the breaker transient recovery voltage are also dealt with in the paper.
引用
收藏
页码:1862 / 1874
页数:13
相关论文
共 50 条
  • [31] TENNESSEE VALLEY AUTHORITYS 500-KV SYSTEM - TRANSMISSION LINE DESIGN
    PFITZER, AC
    WILHOITE, GM
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1966, PA85 (01): : 28 - &
  • [32] Limits and design control of radio interference for 1000 kV AC transmission lines
    Wu, Xiong
    Li, Ni
    Zhang, Guang-Zhou
    Gaodianya Jishu/High Voltage Engineering, 2009, 35 (08): : 1791 - 1795
  • [33] The Simulation Analysis and Research of the Electromagnetic Influence of the 500kV AC Transmission Line On the Seismic Station
    Zhao, Jingyuan
    Liu, Mengxuan
    Xu, Hui
    Ren, Boqiang
    2018 2ND IEEE CONFERENCE ON ENERGY INTERNET AND ENERGY SYSTEM INTEGRATION (EI2), 2018,
  • [34] FIRST 500-KV AC TRANSMISSION-LINE DESIGNS FOR BONNEVILLE POWER ADMINISTEATIONS GRID
    OSIPOVICH, AA
    POLAND, MG
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1965, PA84 (01): : 28 - +
  • [35] Lightning performances for AC 500kV transmission lines with quadruple-circuit on single tower
    Chai, Yajing
    Zhou, Wenjun
    Xue, Li
    Liu, Xiaodong
    Su, Hongmei
    2007 COMPATIBILITY IN POWER ELECTRONICS, 2007, : 83 - 88
  • [36] Typical models of compact transmission lines and application prospect in 500KV AC system of China
    Zhang, B
    Cen, WH
    Huang, JY
    POWERCON '98: 1998 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY - PROCEEDINGS, VOLS 1 AND 2, 1998, : 218 - 222
  • [37] Icing Flashover Characteristics and Discharge Process of 500 kV AC Transmission Line Suspension Insulator Strings
    Liu, Yunpeng
    Gao, Song
    Huang, Daochun
    Yao, Tao
    Wu, Xiong
    Hu, Yi
    Cai, Wei
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (02) : 434 - 442
  • [38] DESIGN OF MICA HYDROELECTRIC PROJECT - MAJOR 500 KV SF6 INSTALLATION
    HANDEL, RD
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1977, 96 (05): : 1535 - 1545
  • [39] Optimizing design on AC filters in Jinping-Sunan ±800 kV UHVDC project
    Li, Jingyan
    Zhang, Zongxin
    Wu, Fangjie
    Gaodianya Jishu/High Voltage Engineering, 2012, 38 (12): : 3224 - 3229
  • [40] Design and Technical Analysis of 500-600 kV HVDC Transmission System for Turkey
    Font, Aytug
    Ilhan, Suat
    Ismailoglu, Hasbi
    Cortes, Fermin Espino
    Ozdemir, Aydogan
    2017 10TH INTERNATIONAL CONFERENCE ON ELECTRICAL AND ELECTRONICS ENGINEERING (ELECO), 2017, : 201 - 205