DRY AND WET-PEAKING TOWER COOLING SYSTEMS FOR POWER-PLANT APPLICATION

被引:0
|
作者
LARINOFF, MW [1 ]
FORSTER, LL [1 ]
机构
[1] INGERSOLL RAND CO,E BRUNSWICK,NJ
来源
COMBUSTION | 1977年 / 48卷 / 11期
关键词
POWER PLANTS - Heat Sinks - WATER COOLING TOWERS - Design;
D O I
暂无
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
A new concept of power plant heat-sink system is presented which employs the combination of a conventional wet-tower and a conventional dry-tower. The purpose of this cooling system is to reduce wet cooling-tower makeup-water requirements in water-short areas. The dry tower operates all year around while the wet-peaking tower is used only above certain ambient dry-bulb temperatures. The two cooling circuits serve separate sections of a conventional, surface-type, steam condenser. Thermal performance analysis is presented for various combinations of cooling systems ranging from 100 percent wet to 100 percent dry. Annual makeup-water requirements are calculated for various sizes of towers located in 18 selected cities of the U. S. A. , ranging from north to south and east to west.