POWER HV CIRCUIT-BREAKERS WITH SEVERE CAPACITIVE SWITCHING DUTY

被引:0
|
作者
CANELHAS, A
BENGTSSON, BA
MARGAARD, T
STRANDEM, A
ALVINSSON, R
机构
[1] ABB POWER SYST,DEPT HVDC SYST DESIGN,LUDVIKA,SWEDEN
[2] ABB HV SWITCHGEAR CO,DIV CIRCUIT BREAKER,LUDVIKA,SWEDEN
[3] ELSAM,DIV TRANSMISS SYST,FREDERICIA,DENMARK
关键词
3-PHASE-FAULTS; FILTER BREAKER; CAPACITIVE SWITCHING; TRV (TRANSIENT RECOVERY VOLTAGE); RESTRIKE CONDITIONS;
D O I
10.1109/61.296265
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The analysis and control of temporary overvoltages at the ac busbars of an HVDC converter station has been treated in great detail [1], [2], [3], [4]. Often it has been found necessary to operate circuit breakers to disconnect a major capacitive load from the main ac buses under severe transient overvoltage conditions. This paper describes results of tests made on a conventional puffer breaker aimed at gaining knowledge of the consequences of a restrike on the breaker itself. The paper also proposes a method to reduce the transient recovery voltage (TRV) requirements imposed on power circuit breakers in order to be able, in most of the cases, to use standard devices for capacitive breaking. The method is based on application of metal-oxide resistors in parallel with the breaker contacts. The phenomena described in this paper are in all aspects valid for any power system which can have the cases here presented. Therefore this paper is not particular only for HVDC converter stations.
引用
收藏
页码:842 / 848
页数:7
相关论文
共 50 条
  • [1] RECENT EXPERIENCE WITH SYNTHETIC CIRCUITS FOR CAPACITIVE CURRENT SWITCHING TESTS ON HV CIRCUIT-BREAKERS
    MANGANARO, S
    ROMITI, A
    ROVELLI, S
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1983, 102 (10): : 3329 - 3337
  • [2] SWITCHING CAPACITIVE CURRENTS WITH MINIMUM OIL CIRCUIT-BREAKERS
    LARSSON, P
    WEHRLI, R
    BROWN BOVERI REVIEW, 1974, 61 (04): : 174 - 178
  • [3] Cascading reliability model for HV circuit-breakers
    Choonhapran, P.
    Balzer, G.
    2007 IEEE LAUSANNE POWERTECH, VOLS 1-5, 2007, : 1770 - 1775
  • [4] LIMITING SWITCHING SURGE OVERVOLTAGES WITH CONVENTIONAL POWER CIRCUIT-BREAKERS
    KONKEL, HE
    LEGATE, AC
    RAMBERG, HC
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1977, 96 (02): : 535 - 542
  • [5] HV DISTRIBUTION CIRCUIT-BREAKERS DESIGNED FOR INFREQUENT ATTENTION
    CATON, PS
    ELECTRICAL REVIEW, 1973, 193 (02): : 50 - 51
  • [6] TESTING OF POWER CIRCUIT-BREAKERS
    URBANEK, J
    ETZ ARCHIV, 1981, 3 (04): : 107 - 112
  • [7] Availability of HV circuit-breakers: The application of Markov model
    Choonhapran, P.
    Balzer, G.
    2007 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-10, 2007, : 424 - +
  • [8] HV dielectric strength of shielding electrodes in vacuum circuit-breakers
    Giere, S
    Kurrat, M
    Schümann, U
    ISDEIV: XXTH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, PROCEEDINGS, 2002, 20 : 119 - 122
  • [9] Electrical endurance tests for HV circuit-breakers : EDF experience
    Jeanjean, R
    Salzard, C
    Migaud, P
    2002 IEEE POWER ENGINEERING SOCIETY WINTER MEETING, VOLS 1 AND 2, CONFERENCE PROCEEDINGS, 2002, : 294 - 298
  • [10] Circuit-Breakers
    Scott, WM