THRESHOLD VOLTAGE FOR ELECTRICAL TREE INCEPTION IN UNDERGROUND HV TRANSMISSION CABLES

被引:24
|
作者
BAMJI, SS
BULINSKI, AT
CHEN, Y
DENSLEY, RJ
机构
[1] National Research Council of Canada, Ottawa, Ontario
[2] Ontario Hydro Research Center, Toronto, Ontario
来源
关键词
D O I
10.1109/14.135612
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Experimental evidence is provided to show that irreversible aging which leads to electrical treeing in polymeric insulation, such as low-density and crosslinked polyethylene used in HV transmission cables, does not start at local fields between 5 and 20 kV/mm. It is shown that a much higher stress is required for electrical tree inception and that the electroluminescence inception voltage is the threshold voltage at which the polymer starts to degrade.
引用
收藏
页码:402 / 404
页数:3
相关论文
共 50 条
  • [21] Inception of electrical tree from water-tree degradation
    Suzuoki, Y.
    Saito, T.
    Komori, F.
    Uchida, K.
    ICPASM 2005: PROCEEDINGS OF THE 8TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 AND 2, 2006, : 111 - +
  • [22] Inception and propagation of electrical tree from water tree degradation
    Suzuoki, Y
    Saito, T
    Morita, M
    Komori, F
    Wu, K
    Kato, T
    Uchida, K
    2004 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2004, : 302 - 305
  • [23] Analysis of Electrical Tree Inception in Silicone Gels
    Mancinelli, Paolo
    Cavallini, Andrea
    Dodd, Stephen J.
    Chalashkanov, Nikola M.
    Dissado, Leonard A.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (06) : 3974 - 3984
  • [24] Influence of AC Voltage Prestressing on AC Electrical-tree Inception of Deteriorated LDPE with Dried Water-tree
    Asai, D.
    Kurimoto, M.
    Komori, F.
    Kato, T.
    Funabashi, T.
    Suzuoki, Y.
    2014 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2014, : 385 - 388
  • [25] Attenuation of Low Frequency Magnetic Fields Produced by HV Underground Power Cables
    Ippolito, Mariano Giuseppe
    Puccio, Andrea
    Ala, Guido
    Ganci, Salvatore
    2015 50TH INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE (UPEC), 2015,
  • [26] Grounding effects of HV and MV underground cables associated with urban distribution substations
    Nahman, JM
    Djordjevic, VB
    Salamon, DD
    IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (01) : 111 - 116
  • [27] Detection of Incipient Faults in Underground Medium Voltage Cables
    Kasztenny, Bogdan
    Voloh, Ilia
    Jones, Christopher G.
    2009 POWER SYSTEMS CONFERENCE, 2009, : 90 - +
  • [28] VERY HIGH VOLTAGE HEAVILY LOADED UNDERGROUND CABLES
    SUTTON, CTW
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1967, PA86 (05): : 571 - &
  • [29] Simulation of Lightning Impulse Voltage Stresses in Underground Cables
    Bhuyan, Kaveri
    Taro, Mudang
    Chatterjee, Saibal
    2015 INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON), 2015, : 34 - 39
  • [30] X-RAY-EXAMINATION OF INSULATION IN LAPPED HIGH-VOLTAGE UNDERGROUND POWER TRANSMISSION CABLES
    MULLER, AC
    MATERIALS EVALUATION, 1979, 37 (10) : P11 - P11