A NONDIMENSIONAL ANALYSIS OF VERTICAL CONFIGURATION, GROUND-COUPLED HEAT-PUMP STARTUP

被引:1
|
作者
DOBSON, MK
ONEAL, DL
WOLFE, ML
机构
[1] VIRGINIA POLYTECH INST & STATE UNIV,DEPT AGR ENGN,BLACKSBURG,VA 24061
[2] TEXAS A&M UNIV SYST,DEPT MECH ENGN,COLL STN,TX 77843
关键词
D O I
10.1115/1.2930053
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
A nominal 10.6 kW (three ton), vertical configuration, ground-coupled heat pump was installed in Abilene, TX in Dec. 1989 and has been monitored since then using a remote data acquisition system. Monitored data include: temperature and relative humidity of return and supply air water temperature entering and leaving the condenser power consumption of the individual system components, cycling rate, on-time, and soil temperatures at various depths and radial locations. Water and airflow rates have been measured twice during the monitored period, and have remained constant. The measured quantities allow calculation of instantaneous capacity, power coefficient of performance (COP), and ground-coil heat rejection. Data for operation in the cooling mode are discussed herein. Based on the experimental data, it was discovered that the water temperature entering the condenser (EWT) exhibited a prolonged minimum after startup due to cooling of the water during the off-cycle. The decreased levels of EWT early in the cycle increased capacity and decreased power both acting to increase the COP. Two sets of nondimensional groups were developed based on the experimental data. The first nondimensional group allowed analysis of startup independent of changes in independent variables, while the second nondimensional group quantified the performance benefits due to cyclic operation. The results tended to indicate that an improvement in COP may be achieved in cyclic operation, due to the decreased values of EWT early in the cycle. This is in contrast to behavior for air source heat pumps, where cycling always degrades efficiency.
引用
收藏
页码:220 / 225
页数:6
相关论文
共 50 条
  • [1] GROUND-COUPLED HEAT-PUMP RESEARCH
    BOSE, J
    PARKER, J
    [J]. ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1983, 25 (05): : 59 - 59
  • [2] GROUND-COUPLED HEAT-PUMP SYSTEM
    DROWN, DC
    DENBRAVEN, KR
    [J]. ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1992, 34 (08): : 14 - 14
  • [3] MULTILAYERED SOIL EFFECTS ON VERTICAL GROUND-COUPLED HEAT-PUMP DESIGN
    DENG, Y
    FEDLER, CB
    [J]. TRANSACTIONS OF THE ASAE, 1992, 35 (02): : 687 - 694
  • [4] Optimization and Analysis of a Vertical Ground-Coupled Heat Pump
    Kord, Ali Siavoshi
    Jazayeri, Seyed Ali
    [J]. INTERNATIONAL JOURNAL OF RENEWABLE ENERGY RESEARCH, 2012, 2 (01): : 33 - 37
  • [5] GROUND-COUPLED HEAT-PUMP SYSTEM EXPERIMENTAL RESULTS
    METZ, P
    [J]. ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1983, 25 (05): : 59 - 59
  • [6] A TRNSYS/GROCS SIMULATION OF A HORIZONTAL COIL GROUND-COUPLED HEAT-PUMP
    CONLIN, F
    JOHNSON, WS
    WIX, S
    [J]. JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 1986, 108 (03): : 185 - 191
  • [7] A GROUND-COUPLED STORAGE HEAT-PUMP SYSTEM WITH WASTE HEAT-RECOVERY
    DROWN, DC
    KAST, TP
    DENBRAVEN, KR
    [J]. ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1992, 34 (02): : 20 - 24
  • [8] THE USE OF GROUND-COUPLED TANKS IN SOLAR-ASSISTED HEAT-PUMP SYSTEMS
    METZ, PD
    [J]. JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 1982, 104 (04): : 366 - 372
  • [9] Operation performance investigation of ground-coupled heat-pump system for temperate region
    Man, Yi
    Yang, Hongxing
    Wang, Jinggang
    Fang, Zhaohong
    [J]. INTERNATIONAL JOURNAL OF LOW-CARBON TECHNOLOGIES, 2011, 6 (02) : 107 - 118
  • [10] Temperature distributions in boreholes of a vertical ground-coupled heat pump system
    Esen, Hikmet
    Inalli, Mustafa
    Esen, Yuksel
    [J]. RENEWABLE ENERGY, 2009, 34 (12) : 2672 - 2679