LOCAL HEAT-TRANSFER BEHAVIOR AND ITS IMPACT ON A SINGLE-ROW, ANNULARLY FINNED TUBE HEAT-EXCHANGER

被引:37
|
作者
HU, X
JACOBI, AM
机构
[1] Department of Mechanical and Industrial Engineering, The University of Illinois at Urbana-Champaign, Urbana, IL
来源
关键词
FINNED SURFACES; FORCED CONVECTION; HEAT EXCHANGERS;
D O I
10.1115/1.2910671
中图分类号
O414.1 [热力学];
学科分类号
摘要
Experimental studies of the local mass transfer characteristics of annularly finned tubes in crossflow are presented. Variations due to boundary layer development, forward-edge separation, the tube wake, horseshoe vortices, and tip vortices are discussed. In addition, regularly located local maxima in mass transfer rates associated with the horseshoe vortex system are found, and conjecture as to their mechanism is offered. Inferring heat transfer behavior from the mass transfer results, we find that the true fin efficiency is always less than that obtained with an assumed constant convective heat transfer coefficient. The difference is 3-7 percent for high-conductivity materials such as aluminum alloys, and 9-17 percent for low-conductivity materials such as mild steels.
引用
收藏
页码:66 / 74
页数:9
相关论文
共 50 条