Radiant panel and air heating performance in large industrial buildings

被引:0
|
作者
Kaiser Ahmed
Esko Sistonen
Raimo Simson
Jarek Kurnitski
Jyrki Kesti
Petteri Lautso
机构
[1] Aalto University,Department of Civil Engineering
[2] Tallinn University of Technology,Faculty of Civil Engineering
[3] Ruukki Construction Oy,undefined
来源
Building Simulation | 2018年 / 11卷
关键词
air heating; ceiling radiant heating; temperature gradient; heating energy use;
D O I
暂无
中图分类号
学科分类号
摘要
This study determined the vertical temperature gradient in two large industrial buildings with room height close to 10 m. One of the buildings was an assembly hall with air heating system and the other was a warehouse equipped with radiant heating (primary) and air heating (secondary) system. The objective of the study was to determine the differences of vertical temperature gradient in halls during the winter. The findings from this study were used in dynamic whole-year simulations for estimating the heating and ventilation energy differences. The results showed about 0.2 K/m vertical temperature gradients in both halls, which was smaller by a factor of 5 for air heating than guidebook. This difference was likely because of the building being ventilated and well insulated. Temperature gradients kept reasonably constant at all measured outdoor temperatures. Energy simulations with measured gradient values of 0.2 K/m and with outdoor airflow rate during occupied hours 1.0 L/(s·m2), which was enough for ventilation and for air heating with simulated good insulation level, resulted in 15% to 41% higher primary energy for air heating. If it is possible to lower outdoor airflow rates to 0.5 L/(s·m2) during occupied hours, which was enough to remove pollutants from occupancy, the analyzed cases showed 23% lower primary energy for radiant heating.
引用
收藏
页码:293 / 303
页数:10
相关论文
共 50 条
  • [1] Radiant panel and air heating performance in large industrial buildings
    Ahmed, Kaiser
    Sistonen, Esko
    Simson, Raimo
    Kurnitski, Jarek
    Kesti, Jyrki
    Lautso, Petteri
    [J]. BUILDING SIMULATION, 2018, 11 (02) : 293 - 303
  • [2] RADIANT PANEL HEATING
    不详
    [J]. MECHANICAL ENGINEERING, 1991, 113 (08) : 16 - 16
  • [3] Role of Radiant Panel Heating and Cooling in Net Zero Energy Buildings
    Kilkis, Birol
    [J]. ASHRAE: TRANSACTIONS 2011, VOL 117, PT 1, 2011, 117 : 602 - 609
  • [4] Performance of Radiant Heating Systems of Low-Energy Buildings
    Sarbu, Ioan
    Mirza, Matei
    Crasmareanu, Emanuel
    [J]. WORLD MULTIDISCIPLINARY CIVIL ENGINEERING-ARCHITECTURE-URBAN PLANNING SYMPOSIUM - WMCAUS, 2017, 245
  • [6] Field evaluation of performance of radiant heating/cooling ceiling panel system
    Li, Rongling
    Yoshidomi, Togo
    Ooka, Ryozo
    Olesen, Bjarne W.
    [J]. ENERGY AND BUILDINGS, 2015, 86 : 58 - 65
  • [7] Numerical and Experimental Study on the Performance of Thermoelectric Radiant Panel for Space Heating
    Lim, Hansol
    Jeong, Jae-Weon
    [J]. MATERIALS, 2020, 13 (03)
  • [8] Comparison of the Floor and Infrared Radiant Heating System in Large-Space Buildings
    Jia, Lizhi
    Liu, Junjie
    Xiao, Wu
    Zhang, Haiqiao
    [J]. PROCEEDINGS OF BUILDING SIMULATION 2019: 16TH CONFERENCE OF IBPSA, 2020, : 1906 - 1912
  • [9] Numerical modelling of high-temperature radiant panel heating system for an industrial hall
    Sarbu, Ioan
    Tokar, Adriana
    [J]. INTERNATIONAL JOURNAL OF ADVANCED AND APPLIED SCIENCES, 2018, 5 (05): : 1 - 9
  • [10] HEATING OF INDUSTRIAL BUILDINGS
    DAVIS, WJ
    [J]. ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1973, 15 (11): : 40 - 44