Performance of Dual Photoelectric/Ionization Smoke Alarms in Full-Scale Fire Tests

被引:0
|
作者
Thomas Cleary
机构
[1] National Institute of Standards and Technology,Building and Fire Research Laboratory
来源
Fire Technology | 2014年 / 50卷
关键词
Smoke alarms; Dual alarms; Fire tests;
D O I
暂无
中图分类号
学科分类号
摘要
Data from two full-scale residential smoke alarm fire test series were analyzed to estimate the performance of dual sensor photoelectric/ionization alarms as compared to co-located individual photoelectric and ionization alarms. Dual alarms and aggregated photoelectric and ionization alarm responses were used to estimate dual alarm performance. It was observed that dual alarms with equivalent or higher sensitivity settings performed better than individual photoelectric or ionization alarms over a range of flaming and smoldering fire scenarios. In one test series, dual alarms activated 539 s faster than ionization alarms and 79 s faster than photoelectric alarms on average. In another test series, individual alarm sensor outputs were calibrated against a reference smoke source in terms of light obscuration over a path length (percent smoke obscuration per unit length) so that alarm thresholds could be defined by the sensor outputs. In that test series, dual alarms, with individual sensor sensitivities equal to their counterpart alarm sensitivities, activated 261 s faster on average than ionization alarms (with sensitivity settings of 4.3%/m smoke obscuration for the ionization sensors) and 35 s faster on average than the photoelectric alarms (with sensitivity settings of 6.6%/m, for the photoelectric sensors.) In cases where an ionization sensor was the first to reach the alarm threshold, the dual alarm activated 67 s faster on average than the photoelectric alarm. While in cases were a photoelectric sensor was the first to reach the alarm threshold, the dual alarm activated 523 s faster on average than the ionization alarm. Over a range of ionization sensor settings examined, dual alarm response was insensitive to the ionization sensor setting for initially smoldering fires and fires with the bedroom door closed, while dual alarm response to the kitchen fires was very sensitive to the ionization sensor setting. Tests conducted in the National Institute of Standards and Technology (NIST) fire emulator/detector evaluator showed that the ionization sensors in off-the-shelf ionization alarms and dual alarms span a range of sensitivity settings. While there appears to be no consensus on sensitivity setting for ionization sensors, it may be desirable to tailor sensor sensitivities in dual alarms for specific applications, such as near kitchens where reducing nuisance alarms may be a goal, or in bedrooms where higher smoke sensitivity may be a goal.
引用
收藏
页码:753 / 773
页数:20
相关论文
共 50 条
  • [1] Performance of Dual Photoelectric/Ionization Smoke Alarms in Full-Scale Fire Tests
    Cleary, Thomas
    [J]. FIRE TECHNOLOGY, 2014, 50 (03) : 753 - 773
  • [2] Analysis of full-scale fire tests
    Auguin, G
    Forestier, BE
    Giovannelli, G
    Casalé, E
    [J]. 10TH INTERNATIONAL SYMPOSIUM ON AERODYNAMICS AND VENTILATION OF VEHICLE TUNNELS: PRINCIPLES, ANALYSIS AND DESIGN, 2000, (43): : 659 - 669
  • [3] Full-scale and reduced-scale tests on smoke movement in case of car park fire
    Horvath, Istvan
    van Beeck, Jeroen
    Merci, Bart
    [J]. FIRE SAFETY JOURNAL, 2013, 57 : 35 - 43
  • [4] Full-scale fire tests in the underwater tunnel section model with sidewall smoke extraction
    Jiang, Yaqiang
    Zhang, Tianhang
    Liu, Shuai
    He, Qinli
    Li, Le
    Huang, Xinyan
    [J]. TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2022, 122
  • [5] A BIBLIOGRAPHY ON FULL-SCALE FIRE TESTS OF FURNISHINGS
    HILADO, CJ
    HUTTLINGER, PA
    [J]. JOURNAL OF CONSUMER PRODUCT FLAMMABILITY, 1980, 7 (04): : 262 - 268
  • [6] Full-scale fire tests on hollowcore floors
    Bailey, C.G.
    Lennon, T.
    [J]. Structural Engineer, 2008, 86 (06): : 33 - 39
  • [7] Full-scale fire tests on complete buildings
    Moore, DB
    [J]. FIRE, STATIC AND DYNAMIC TESTS OF BUILDING STRUCTURES, 1997, : 3 - 15
  • [8] Ionization and photoelectric smoke alarms in rural Alaskan homes
    Fazzini, TM
    Perkins, R
    Grossman, D
    [J]. WESTERN JOURNAL OF MEDICINE, 2000, 173 (02): : 89 - 92
  • [9] Full-scale smoke toxicity tests in furnished rooms
    Belles, D.W.
    [J]. Fire journal Boston, Mass., 1985, 79 (02): : 35 - 41
  • [10] SYSTEMS FOR ANIMAL EXPOSURE IN FULL-SCALE FIRE TESTS
    HILADO, CJ
    CUMMING, HJ
    KOURTIDES, DA
    PARKER, JA
    [J]. JOURNAL OF COMBUSTION TOXICOLOGY, 1977, 4 (02): : 101 - 113