Switching of the vacuum-arc discharge direct current

被引:0
|
作者
E. F. Prozorov
K. N. Ul’yanov
V. A. Fedorov
机构
[1] Lenin All-Russia Electrotechnical Institute (FGUP VEI),Federal State Unitary Enterprise
来源
High Temperature | 2014年 / 52卷
关键词
Magnetic Field; Discharge Chamber; Pulse Magnetic Field; Cathode Spot; Current Interruption;
D O I
暂无
中图分类号
学科分类号
摘要
Interruption of the direct current of a vacuum-arc discharge (VAD) is analyzed with three methods: the connection of a shunt circuit with a capacitor to the discharge chamber, the overlaying of a pulse nonhomogeneous axisymmetric magnetic field upon the discharge, and the combined action of the magnetic field and the shunt circuit. The probability of interruption of the current I = 500 A as a function of the magnetic field induction is obtained for various shunt capacitances within the range 25 ≤ C ≤ 2500 microfarad (μF). It is shown that the probability of interruption for a given magnetic field induction increases as the capacitance is raised and for the given capacitance it increases as the induction is increased. The magnitude of the magnetic system current Im to ensure the current interruption with the probability P = 1 is obtained as a function of the shunt capacitance. The impact of the shunt circuit parameters upon the arc current is analyzed. The time-domain plot of the arc current for the shunt capacitor C = 2500 μF was estimated. Its results agree with the experiment. It is shown that the combined use of the magnetic field and the capacitive shunt circuit is an effective method of VAD direct current interruption.
引用
下载
收藏
页码:179 / 184
页数:5
相关论文
共 50 条