Condition Assessment of DC XLPE Cables Based on Combination Weighting Method

被引:0
|
作者
Zhu, Yufeng [1 ]
Wang, Siyuan [2 ]
Li, Cong [2 ]
Xu, Yongpeng [1 ]
Sheng, Gehao [1 ]
Jiang, Xiuchen [1 ]
机构
[1] Shanghai Jiao Tong Univ, Dept Elect Engn, Shanghai, Peoples R China
[2] State Grid Jinan Elect Power Supply Co, Jinan, Peoples R China
基金
国家重点研发计划;
关键词
Condition assessment; DC XLPE cables; Combination weighting method; FAHP; Anti-entropy method;
D O I
10.1007/978-3-030-31676-1_43
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Aiming at condition assessment for multiple characteristics, this paper proposes the combination weighting method to make full use of information detected by routine tests. Fuzzy analytical hierarchy process (FAHP) is a modified subject weighting method and anti-entropy method is a modified objective weighting method. Combination weighting method combines FAHP and anti-entropy method to get the more reasonable results. First, the index system of DC XLPE cables are established. Second, weight parameters of each index are calculated by FAHP and anti-entropy method. Third, associating weight parameters calculated above, weight parameters of combination weighting method are deduced. Then, calculate the relative degree of deterioration and degree of membership of each index. Finally, use weight vector calculated by combination weighting method and degree of membership matrix to get the condition membership. Compared to FAHP and anti-entropy method, combination weighting method has more smooth distribution of membership and can reflect the potential faults according to some sensitive indexes.
引用
收藏
页码:449 / 457
页数:9
相关论文
共 50 条
  • [1] Condition Assessment of XLPE Insulated Cables Based on Polarization/Depolarization Current Method
    Ye, Gang
    Li, Hua
    Lin, Fuchang
    Tong, Jin
    Wu, Xiaogang
    Huang, Zeqi
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (02) : 721 - 729
  • [2] A Novel Condition Assessment Method for Corrugated Aluminum Sheathed XLPE Cables Based on Evolved Gas Analysis
    Kong, Jiamin
    Zhou, Kai
    Chen, Yidong
    Meng, Pengfei
    Li, Yuan
    Ren, Xiancheng
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2023, 30 (02) : 883 - 891
  • [3] Condition assessment of 15 kV rejuvenated underground XLPE cables
    Ogawa, Lisa E.
    Abdolall, Kal
    Stephens, Mike J.
    Smith, Brent
    [J]. CONFERENCE RECORD OF THE 2008 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 2008, : 698 - +
  • [4] Water treeing and condition assessment of high voltage XLPE cables
    Hvidsten, S
    Faremo, H
    Eriksson, R
    Min, W
    [J]. CONFERENCE RECORD OF THE 2002 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2002, : 112 - 115
  • [5] Experience from on-site condition assessment of XLPE MV cables
    Skjolberg, Johan
    Hvidsten, Sverre
    Farmeo, Hallvard
    [J]. CONFERENCE RECORD OF THE 2006 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2006, : 432 - +
  • [6] The Application of Partial Discharge Detection for the condition assessment of XLPE Power Cables
    Zhou, Xiaoli
    Qian, Yong
    Liu, Muqing
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2012, 88 (06): : 313 - 316
  • [7] Risk Assessment of XLPE Power Cables Based on Fuzzy Comprehensive Evalution Method
    Huan, Jia-jia
    Wang, Gang
    Li, Hai-feng
    Sun, Zhi-bin
    [J]. 2010 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2010,
  • [8] Combination Weighting Method Based on Maximizing Deviations and Normalized Constraint Condition
    Yin, Fulian
    Lu, Lu
    Chai, Jianping
    Yang, Yanbing
    [J]. INTERNATIONAL JOURNAL OF SECURITY AND ITS APPLICATIONS, 2016, 10 (02): : 39 - 50
  • [9] The Condition Assessment System of XLPE Cables Using the Isothermal Relaxation Current Technique
    Wu, Jiandong
    Yin, Yi
    Li, Xuguang
    Wang, Yaqun
    Xiao, Dengming
    [J]. ICPADM 2009: PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1-3, 2009, : 1114 - 1117
  • [10] Health condition assessment of MV XLPE and bare cables. Case study
    Rosero, Laura
    Cardenas, Luis A.
    Garzon, Camilo
    Teran, Daniel
    Nova, David
    Herrera, Fernando
    Diaz, Jennifer
    Valbuena, Ivan
    Garcia, Rodolfo
    [J]. IFAC PAPERSONLINE, 2023, 56 (02): : 6618 - 6623