Insulation structure design and electric field simulation of 500 kV isolation energy supply transformer for HVDC breaker

被引:7
|
作者
Zhang, Sheng [1 ,2 ]
Fan, Yadong [1 ]
Lei, Qingquan [3 ]
Wang, Jianguo [1 ]
Liu, Yuan [2 ]
Zhan, Ting [4 ]
机构
[1] Wuhan Univ, Sch Elect Engn & Automat, Wuhan 430072, Peoples R China
[2] Global Energy Interconnect Res Inst Co Ltd, Beijing, Peoples R China
[3] Qingdao Univ Sci & Technol, Inst Adv Elect Mat, Qingdao, Peoples R China
[4] China EPRI Elect Power Engn Co Ltd, Beijing, Peoples R China
关键词
Electric insulation - Electric windings - Rubber - Electric fields - DC transformers - Shielding;
D O I
10.1049/hve2.12102
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The high-voltage isolated energy supply transformer (HIET) is the key component of the HVDC breaker, which is used for energy transmission and the potential isolation. There is a lack of research results that can meet engineering applications at home and abroad. The design of a 500 kV HIET with dry-type insulation is proposed, using 10 cascade connected 50 kV sub-transformers (STs), which uses silicon rubber suitable for DC voltage as the main insulation material. High-voltage (HV) winding of ST adopts double-shielding structure of coil semi-conductive shielding and inner semi-conductive shielding to improve electric field distribution. The simulation analysis of an electric field at different insulation thicknesses and temperatures shows that the electric field decreases with an increase in thickness of insulation. When the thickness is greater than 25 mm, the electric field reduction effect is significantly weakened. The electric field is closely related to temperature, when at 20 degrees C, the electric field between double-shielding is relatively uniform. When at 70 degrees C, the inner shielding electric field is much higher than coil shielding, and undergoes obvious reversal. In addition, the 500 kV HIET's electric field has been analysed. The 50 0kV HIET prototype has been manufactured and passed the type test, and successfully applied to the 500 kV Zhangbei DC grid project.
引用
收藏
页码:185 / 196
页数:12
相关论文
共 50 条
  • [1] Winding Overvoltage Characteristic Analysis of Modular Cascade Isolating Energy Supply Transformer of ±500 kV Hybrid HVDC Breaker
    Zhang, Sheng
    Fan, Yadong
    Wang, Jianguo
    Liu, Yuan
    Zhou, Wandi
    IEEE TRANSACTIONS ON POWER DELIVERY, 2023, 38 (02) : 1248 - 1258
  • [2] Current transformer failure caused by electric field associated to circuit breaker and pollution in 500 kV substations
    Arias Velasquez, Ricardo Manuel
    Mejia Lara, Jennifer Vanessa
    ENGINEERING FAILURE ANALYSIS, 2018, 92 : 163 - 181
  • [3] Electric field simulation and optimization of ±1100 kV HVDC converter valve in insulation type test
    Qi, Lei
    Wang, Xingxing
    Li, Chao
    Wang, Gaoyong
    Cui, Xiang
    Gao, Chong
    Gaodianya Jishu/High Voltage Engineering, 2015, 41 (04): : 1262 - 1271
  • [4] Research on Insulation Design of 500kV DC Circuit Breaker Support
    Ouyang W.
    Yang J.
    Wang C.
    Zhang S.
    Wu X.
    Dianwang Jishu/Power System Technology, 2020, 44 (03): : 1175 - 1179
  • [5] Electric Field Computation and Insulation Structure Optimization for DC ±500kV Composite Tower
    Yang, Xi
    Zhu, Lijuan
    Zhu, Shenglong
    Qin, Shaorui
    Zhan, Xuhai
    2022 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (IEEE CEIDP 2022), 2022, : 527 - 530
  • [6] Improvement of Main Insulation Structure for 110kV Electric Power Transformer based on Electric Field Analysis
    Gao Youhua
    Gao Dan
    Li Yanbin
    Gong Shuqiu
    Wang Guogang
    ICEMS 2008: PROCEEDINGS OF THE 11TH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS 1- 8, 2008, : 4427 - +
  • [7] 3D Electric Field Simulation of Converter Transformer with Real Insulation Materials Utilized in HVDC Systems
    Sun, Weidong
    Yang, Lijun
    Hao, Jian
    Zare, Firuz
    2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2018,
  • [8] Electric field analysis of the insulation structure of power transformer
    Makuc, D
    Ikanovic, J
    Lenasi, K
    Computer Engineering in Applied Electromagnetism, 2005, : 155 - 160
  • [9] Electric-field Simulation of Insulation Type Test of ± 420kV HVDC Flexible Converter Valve
    Liu, Chenyang
    Han, Kun
    Yao, Weizheng
    Hu, Siquan
    Zheng, Xiaoquan
    2018 IEEE INTERNATIONAL POWER ELECTRONICS AND APPLICATION CONFERENCE AND EXPOSITION (PEAC), 2018, : 2092 - 2095
  • [10] Design for New Type of Main Insulation of 35kV Electric Power Transformer Based on Electric Field Analysis
    Liu, Yanju
    Cao, Yundong
    Li, Yanbin
    Gao, Youhua
    Liu, Xiaoming
    2008 WORLD AUTOMATION CONGRESS PROCEEDINGS, VOLS 1-3, 2008, : 896 - +