Drop-in energy performance evaluation of R1234yf and R1234ze(E) in a vapor compression system as R134a replacements

被引:217
|
作者
Mota-Babiloni, Adrian [1 ,2 ]
Navarro-Esbri, Joaquin [2 ]
Barragan, Angel [2 ]
Moles, Francisco [2 ]
Peris, Bernardo [2 ]
机构
[1] Univ Politecn Valencia, Inst Ind Radiophys & Environm Safety, E-46022 Valencia, Spain
[2] Univ Jaume 1, Dept Mech Engn & Construct, ISTENER Res Grp, E-12071 Castellon de La Plana, Spain
关键词
Drop-in; Energy performance; R1234yf; R1234ze(E); R134a; Vapor compression system; AIR-CONDITIONING SYSTEM; HEAT-TRANSFER; BINARY-MIXTURES; HFO-1234YF; WORKING; R-1234ZE(E); PROPERTY;
D O I
10.1016/j.applthermaleng.2014.06.056
中图分类号
O414.1 [热力学];
学科分类号
摘要
This paper presents an energy performance evaluation of two low-GWP refrigerants, R1234yf and R1234ze(E), as drop-in replacements for R134a. Tests are carried out in a monitored vapor compression system combining different values of evaporation and condensation temperature, and without/with the adoption of an internal heat exchanger. The parameters analyzed are volumetric efficiency, cooling capacity and COP and they are presented taking R134a as baseline. Results show that without IHX the average volumetric efficiency for R1234yf and R1234ze is 4% and 5% lower compared with R134a. The cooling capacity obtained with R1234yf and R1234ze is reduced, with an average difference of 9% and 30% without IHX. Also, COP values are about 7% lower for R1234yf and 6% lower for R1234ze than those obtained using R134a. Finally, the use of an internal heat exchanger reduces the COP differences for both replacements. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:259 / 265
页数:7
相关论文
共 50 条
  • [1] Performance Evaluation of Centrifugal Refrigeration Compressor Using R1234yf and R1234ze(E) as Drop-In Replacements for R134a Refrigerant
    Yi, Kexin
    Zhao, Yuanyang
    Liu, Guangbin
    Yang, Qichao
    Yu, Guoxin
    Li, Liansheng
    [J]. ENERGIES, 2022, 15 (07)
  • [2] Thermodynamic and heat transfer analyses for R1234yf and R1234ze(E) as drop-in replacements for R134a in a small power refrigerating system
    Jankovic, Zvonimir
    Sieres Atienza, Jaime
    Martinez Suarez, Jose Antonio
    [J]. APPLIED THERMAL ENGINEERING, 2015, 80 : 42 - 54
  • [3] Exergy analysis of R1234yf and R1234ze as R134a replacements in a two evaporator vapour compression refrigeration system
    Yataganbaba, Alptug
    Kilicarslan, Ali
    Kurtbas, Irfan
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2015, 60 : 26 - 37
  • [4] Computational energy and exergy analysis of R134a, R1234yf, R1234ze and their mixtures in vapour compression system
    Gaurav
    Kumar, Raj
    [J]. AIN SHAMS ENGINEERING JOURNAL, 2018, 9 (04) : 3229 - 3237
  • [5] Performance evaluation of VCR system with pure and various blends of R134a, R1234yf, and R1234ze (E) refrigerants
    Kuwar, Yogendra Vasantrao
    [J]. HEAT TRANSFER, 2024, 53 (06) : 2879 - 2904
  • [6] ENERGY AND EXERGY INVESTIGATIONS OF R1234yf AND R1234ze AS R134a REPLACEMENTS IN MECHANICALLY SUBCOOLED VAPOUR COMPRESSION REFRIGERATION CYCLE
    Agarwal, Shyam
    Arora, Akhilesh
    Arora, B. B.
    [J]. JOURNAL OF THERMAL ENGINEERING, 2021, 7 (01): : 109 - 132
  • [7] Experimental analysis of R1234yf as a drop-in replacement for R134a in a vapor compression system
    Navarro-Esbri, J.
    Mendoza-Miranda, J. M.
    Mota-Babiloni, A.
    Barragan-Cervera, A.
    Belman-Flores, J. M.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2013, 36 (03): : 870 - 880
  • [8] Analysis the characteristics of R1234yf, R1234ze, R134a on reefer container
    Ding, Defeng
    Zhu, Zhenxiang
    Chen, Wu
    Liu, Shijie
    Zheng, Chaoyu
    [J]. 2019 5TH INTERNATIONAL CONFERENCE ON ADVANCES IN ENERGY RESOURCES AND ENVIRONMENT ENGINEERING (ICAESEE 2019), 2020, 446
  • [9] R1234yf and R1234ze(E) as environmentally friendly replacements of R134a: Assessing flow boiling on an experimental basis
    Longo, Giovanni A.
    Mancin, Simone
    Righetti, Giulia
    Zilio, Claudio
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 108 : 336 - 346
  • [10] Experimental analysis of the use of R1234yf and R1234ze(E) as drop-in alternatives of R134a in a water-to-water heat pump
    Maria Colombo, Luigi Pietro
    Lucchini, Andrea
    Molinaroli, Luca
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 115 : 18 - 27