Experimental study on the dynamic performance of a novel system combining natural ventilation with diffuse ceiling inlet and TABS

被引:16
|
作者
Yu, Tao [1 ,2 ]
Heiselberg, Per [2 ]
Lei, Bo [1 ]
Zhang, Chen [2 ]
Pomianowski, Michal [2 ]
Jensen, Rasmus [2 ]
机构
[1] Southwest Jiaotong Univ, Sch Mech Engn, Chengdu 610031, Peoples R China
[2] Aalborg Univ, Dept Civil Engn, DK-9000 Aalborg, Denmark
关键词
Natural ventilation; Thermally activated building systems (TABS); Diffuse ceiling inlet; Dynamic performance; Control strategy; Thermal comfort; BUILDING SYSTEMS; COMFORT PERFORMANCE; NIGHT VENTILATION; ENERGY; AIR; DESIGN; WARM; MASS;
D O I
10.1016/j.apenergy.2016.01.116
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper investigates the dynamic cooling performance of a novel system combining natural ventilation with diffuse ceiling inlet and thermally activated building systems (TABS). This system is tested in the lab under three climatic conditions representing typical seasons in Denmark, including a typical winter day, a typical day in the transitional season and a typical summer day. The corresponding dynamic control strategies have been designed for these three cases in the measurements. In the winter case, TABS have to be activated for two hours to supply extra heating to ensure a comfortable indoor environment. In the case representing the transitional season, changing the ventilation rate during both occupied and un-occupied hours can ensure the thermal autonomy of the room without extra heating or cooling from TABS. In the summer case, the free cooling potential of ventilation air is limited due to the relatively high inlet air temperature. Therefore, TABS are activated for ten hours to supply the.extra cooling. Due to the use of the diffuse ceiling, the whole-body and local thermal comfort conditions are quite good in the measurements. The dynamic measurements in the paper are beneficial to the future design and application of this system. (C) 2016 Elsevier Ltd. All rights reserved.
引用
下载
收藏
页码:218 / 229
页数:12
相关论文
共 50 条
  • [1] Experimental investigation of cooling performance of a novel HVAC system combining natural ventilation with diffuse ceiling inlet and TABS
    Yu, Tao
    Heiselberg, Per
    Lei, Bo
    Pomianowski, Michal
    Zhang, Chen
    Jensen, Rasmus
    ENERGY AND BUILDINGS, 2015, 105 : 165 - 177
  • [2] Experimental investigation on the ventilation performance of diffuse ceiling ventilation in heating conditions
    Peng, Pei
    Pomianowski, Michal
    Zhang, Chen
    Guo, Rui
    Jensen, Rasmus Lund
    Jonsson, Kim Trangbaek
    Gong, Guangcai
    BUILDING AND ENVIRONMENT, 2021, 205
  • [3] Experimental study on the performance of hybrid ventilation system combining forced longitudinal flow and shaft natural ventilation in tunnels
    Yang, Dong
    Dong, Song
    He, Miao
    Zhang, Zhongjie
    Du, Tao
    Ji, Wenhui
    TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2020, 103
  • [4] A novel solution for school renovations: Combining diffuse ceiling ventilation with double skin facade
    Bugenings, Laura Annabelle
    Schaffer, Markus
    Larsen, Olena Kalyanova
    Zhang, Chen
    JOURNAL OF BUILDING ENGINEERING, 2022, 49
  • [5] Performance analysis of a new design of office diffuse ceiling ventilation system
    Fan, Jianhua
    Hviid, Christian Anker
    Yang, Honglu
    ENERGY AND BUILDINGS, 2013, 59 : 73 - 81
  • [6] Performance optimization of a sidewall radiant heating system integrated with diffuse ceiling ventilation
    Yang, Bin
    Guo, Yuyao
    Xu, Shuaixing
    Su, Wei
    Wu, Mengchun
    Wang, Faming
    BUILDING AND ENVIRONMENT, 2022, 213
  • [7] Experimental investigation of an integrated renovation solution combining diffuse ceiling ventilation and double skin façade
    Zhang, Chen
    Larsen, Olena Kalyanova
    Hu, Yue
    Mikkelsen, Asbjorn Kaagaard
    Pedersen, Lotte Louise
    Nyborg, Victor Orsoe
    Larsen, Tine Steen
    BUILDING AND ENVIRONMENT, 2023, 246
  • [8] Experimental comparison of thermal conditions in office rooms: Diffuse ceiling ventilation, chilled beam system, and chilled ceiling combined with mixing ventilation
    Lestinen, Sami
    Mustakallio, Panu
    Kilpelainen, Simo
    Kosonen, Risto
    Jokisalo, Juha
    Koskela, Hannu
    Melikov, Arsen Krikor
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2020, 26 (05) : 631 - 642
  • [9] Experimental study of ventilation performance and contaminant distribution of underfloor ventilation systems vs. traditional ceiling-based ventilation system
    Chao, CY
    Wan, MP
    INDOOR AIR, 2004, 14 (05) : 306 - 316
  • [10] Experimental study of diffuse ceiling ventilation coupled with a thermally activated building construction in an office room
    Zhang, Chen
    Heiselberg, Per Kvols
    Pomianowski, Michal
    Yu, Tao
    Jensen, Rasmus Lund
    ENERGY AND BUILDINGS, 2015, 105 : 60 - 70