Fire Test of Profile Plank for Transformer Pit Fire Protection

被引:2
|
作者
Lindstrom, Johan [1 ]
Forsth, Michael [1 ]
机构
[1] SP Tech Res Inst Sweden, SP Fire Res, POB 857, SE-50115 Boras, Sweden
关键词
Transformer pit; Transformer oil; Transformer fire; Profile plank; Thermocouples; Gas analysis;
D O I
10.1007/s10694-014-0409-2
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
In general it is recommended to fill a transformer pit with rock ballast to extinguish the fire if there is a leakage of burning transformer oil. There is a lack of technology-neutral performance requirements for the design of solutions for fire extinguishment in transformer pit fires. This hampers the introduction of alternatives to the traditional method of filling the pit with rocks. Therefore we have conducted quantitative tests where temperatures and concentrations of CO, CO2, and O-2 were measured at different position in a transformer pit subjected to burning oil simulating an accidental rupture and leakage. The tests were conducted to investigate the extinguishing capacity of one specific alternative solution, i.e. a profile plank layer over the pit. Three tests were performed with 90A degrees C and 140A degrees C pre-heated transformer oil. In the second test, a 19 cm water bed was used to examine the impact of rain water in the pit. The result showed that the profile plank extinguished the flames in a few seconds and that the water level did not have any significant effect on the result. The measurements showed that the temperatures peaked at 600-800A degrees C 50 cm above the profile plank in all tests but dropped to under 100A degrees C in 14-16 s. Furthermore the O-2-concentration dropped to 3-5 vol% below the plank, which contributed to the rapid extinction of the burning oil.
引用
收藏
页码:309 / 319
页数:11
相关论文
共 50 条