Oil entrainment in vertical refrigerant piping

被引:23
|
作者
Kesim, SC [1 ]
Albayrak, K [1 ]
Ileri, A [1 ]
机构
[1] Middle E Tech Univ, Dept Mech Engn, TR-06531 Ankara, Turkey
关键词
refrigerating circuit; piping; vertical tube; oil return; refrigerant; vapour; speed; calculation;
D O I
10.1016/S0140-7007(99)00085-7
中图分类号
O414.1 [热力学];
学科分类号
摘要
The aim of this study is to investigate the required refrigerant speed, hence minimum refrigeration load, for carrying the lubricating oil up in vertical sections of refrigerant lines. It is assumed that the downward flow of the thin oil layer over the inner surface of the riser due to gravity is to be balanced with the upward flow of the oil film due to the shear force created by the upward flow of the refrigerant vapor. Velocities are converted to refrigeration capacities by considering a saturated cycle between specified condenser and evaporator pressures. General relationships thus developed are enumerated for R134a by preparing minimum capacity tables for copper suction and discharge risers. (C) 2000 Elsevier Science Ltd and IIR. All rights reserved.
引用
收藏
页码:626 / 631
页数:6
相关论文
共 50 条
  • [1] REFRIGERANT PIPING
    JONES, RA
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1990, 32 (11): : 12 - 12
  • [2] Air entrainment into water in an overflow piping (air entrainment into annular water flow in a vertical pipe)
    Hattori, N.
    Enomoto, K.
    Nippon Kikai Gakkai Ronbunshu, B Hen/Transactions of the Japan Society of Mechanical Engineers, Part B, 1996, 62 (597): : 1768 - 1773
  • [3] REFRIGERANT PIPING CODES
    DUPERNELL, PC
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1991, 33 (06): : 11 - 11
  • [4] 10 tips for refrigerant piping
    Kuespert, DR
    ASHRAE JOURNAL, 2004, 46 (03) : 48 - +
  • [5] Insulation systems for refrigerant piping
    ASHRAE Handbook, 2002,
  • [6] PARALLELING AS A REFRIGERANT PIPING TECHNIQUE.
    Denkmann, James L.
    HPAC Heating, Piping, Air Conditioning, 1986, 58 (04): : 97 - 100
  • [7] Corrosion and degradation behavior of aluminum and copper refrigerant piping
    Uchiyama, Seiji
    Uemura, Satoshi
    Hiraoka, Koji
    Kimura, Yuji
    Seki, Shiro
    MATERIALS AND CORROSION-WERKSTOFFE UND KORROSION, 2023, 74 (03): : 344 - 351
  • [8] Modeling of minimum refrigerant velocity for oil return and application in designing vertical suction pipes
    School of Mechanical Engineering, Shanghai Jiaotong University, Shanghai 200240, China
    Jixie Gongcheng Xuebao, 2008, 4 (179-183):
  • [9] Mixing oil and refrigerant
    Refrigeration Service & Contracting, 1994, 62 (10):
  • [10] Analysis of Entrainment Ratio about Solar Ejector Refrigerant System
    Zheng, HuiFan
    Liang, YaoHua
    Huang, LanYu
    2012 INTERNATIONAL CONFERENCE ON FUTURE ENERGY, ENVIRONMENT, AND MATERIALS, PT A, 2012, 16 : 516 - 521