A PRACTICAL APPLICATION OF IEEE STD 1584-2018

被引:0
|
作者
Reeves, Adam [1 ]
Freyenberger, Mark [2 ]
Hodder, Michael [3 ]
机构
[1] Eaton, 7451 Coca Cola Dr, Hanover, MD 21076 USA
[2] Eaton, 50 Soccer Pk Dr, Fenton, MO 63026 USA
[3] Eaton, 610 Ind Dr,Unit 2, Milton, ON L9T 5C3, Canada
关键词
Arcing fault current; arc flash; arc-flash boundary; arc-flash hazard analysis; bus gap; electrode configuration; enclosure dimensions; IEEE; 1584; incident energy; working distance;
D O I
10.1109/PCIC42579.2021.9729025
中图分类号
O646 [电化学、电解、磁化学];
学科分类号
081704 ;
摘要
The IEEE Std. 1584-2018 Guide for Performing Arc-Flash Hazard Calculations presents new challenges in data gathering and equipment modeling due to the removal of the 125 kVA exception and the addition of the ability to model electrode configurations, enclosure dimensions, and bus gaps. Engineers must now understand equipment construction and choose whether to field measure equipment and use actual data, or use the typical values presented in IEEE-Std.1584-2018. This paper will discuss how incident energy (IE) and arc-flash boundary (AFB) are affected by electrode configuration, enclosure size and bus gap. This will be demonstrated for various equipment types to determine the practical impact of conservative assumptions. It will also discuss the implications of the new statement regarding arc sustainability at < 2000 A and provide suggested guidelines for the selection of electrode configuration based on examination of real-world equipment construction.