A newly developed line protection with ethernet communication interface based on IEC61850

被引:0
|
作者
Hou, Hui [1 ]
You, Dahai [1 ]
Yin, Xianggen [1 ]
Xu, Tianqi [1 ]
Jin, Mingliang [1 ]
He, Xiongkai [2 ]
Wang, Bo [1 ]
Xie, Yubing [3 ]
机构
[1] Huazhong Univ Sci & Technol, Coll Elect & Elect Engn, Wuhan 430074, Peoples R China
[2] Cent Southern China, Elect Power Design Inst, Wuhan 430071, Peoples R China
[3] China Southern Grid EHV Power Transmiss Co, Guangzhou 510623, Guangdong, Peoples R China
基金
中国国家自然科学基金;
关键词
communication system interfaces; protocols; power system protection;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
As more and more users require the microprocessor protection device has Ethernet interface based on IEC61850, a newly developed relay protection equipment based on DSP with Ethernet communication interface is introduced. The hardware circuit design, drive program and TCP/IP protocols are developed in detail to explain how to realize the Ethernet communication. We use DSP TMS320VC33 as the hardware platform and RTL8019AS as the Ethernet control chip. RTL8019AS is connected with DSP by (Complex Programmable Logic Device) CPLD. The Integral layer model for Ethernet communication is a seven layers model based on IEC61850. The transport layer uses UDP protocol to transport data, as it is faster and more efficient. It can finish the Ethernet communication task and switch to other tasks by sending out and releasing signals to DSP. Experiment shows that it can satisfy 110kV line and below voltage relay protection's technology requirement to Ethernet communication successfully.
引用
收藏
页码:91 / +
页数:3
相关论文
共 50 条
  • [1] Design of line protection IED based on IEC61850 for traction substation
    Wei, Baoquan
    Lin, Zhiming
    [J]. Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2010, 30 (09): : 122 - 124
  • [2] Novel protection scheme based on IEC61850
    Garcia-Gracia, M.
    Borroy, S.
    Gimenez de Urtasun, L.
    Comech, M. P.
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2011, 81 (12) : 2178 - 2187
  • [3] Gigabit Ethernet Based Substation under IEC61850 standard
    Raza, Ali
    Ullah, Khalil
    Ahmed, Saleem
    Ahmed, Salman
    Jang, Hyuk-Soo
    Yang, Hyo-Sik
    [J]. 2009 2ND INTERNATIONAL CONFERENCE ON COMPUTER, CONTROL AND COMMUNICATION, 2009, : 222 - +
  • [4] Design of IED based on IEC61850 standard for distribution system line protection
    Xu, Bin
    Liu, Zi-Ying
    [J]. Dianli Zidonghua Shebei / Electric Power Automation Equipment, 2007, 27 (09): : 103 - 106
  • [5] Design and application of fiber industrial ethernet switch based on IEC61850
    Wang, Qiang
    [J]. Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2010, 38 (13): : 113 - 115
  • [6] Reliability of Substation Protection System Based on IEC61850
    熊小伏
    于军
    刘晓放
    沈智健
    [J]. Transactions of Tianjin University, 2008, (02) : 118 - 122
  • [7] Research on dual network communication based on IEC61850
    Wang, Hai-Feng
    Ding, Jie
    Chen, Ai-Lin
    [J]. Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2009, 37 (03): : 76 - 78
  • [8] Reliability of substation protection system based on IEC61850
    Xiong X.
    Yu J.
    Liu X.
    Shen Z.
    [J]. Transactions of Tianjin University, 2008, 14 (2) : 118 - 122
  • [9] Study of Communication Gateway Based on IEC61850 Protocol
    Qu Zhijian
    Liu Mingguang
    Jiang Zhiling
    Wu Feng
    Liu Jing
    Sun Lichao
    [J]. PROCEEDINGS OF THE INTERNATIONAL CONFERENCE ON COMMUNICATION SOFTWARE AND NETWORKS, 2009, : 659 - +
  • [10] Ethernet Communication Based on the IEC61850-line Monitoring of Electrical Equipment IED
    Liu, Yunpeng
    Wei, Hong
    Wang, Liang
    Zhao, Tao
    [J]. PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 774 - 777