Load-Damping Characteristic Control Method in an Isolated Power System With Industrial Voltage-Sensitive Load

被引:32
|
作者
Liao, Siyang [1 ]
Xu, Jian [1 ]
Sun, Yuanzhang [1 ]
Gao, Wenzhong [2 ]
Ma, Xi-Yuan [3 ]
Zhou, Mi [1 ]
Qu, Yinpeng [1 ]
Li, Xiaomin [4 ]
Gu, Junhe [5 ]
Dong, Jianxun [5 ]
机构
[1] Wuhan Univ, Sch Elect Engn, Wuhan 430072, Peoples R China
[2] Univ Denver, Dept Elect & Comp Engn, Denver, CO 80210 USA
[3] Elect Power Res Inst China Southern Power Grid, Guangzhou 510080, Guangdong, Peoples R China
[4] China Power Investment Corp, Dept Technol & Informat, Beijing 100140, Peoples R China
[5] CPI Energy Grp Meng Dong Grp, Inner Mongolia 028000, Inner Mongolia, Peoples R China
基金
中国国家自然科学基金;
关键词
Industrial voltage-sensitive load; isolated power systems; load-damping characteristic control; system frequency response; ALUMINUM PRODUCTION; FREQUENCY CONTROL; WIND; MANAGEMENT; COAL;
D O I
10.1109/TPWRS.2015.2424240
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Load-damping characteristic models the load response to the frequency deviation, which has important impact on system frequency response. The load-damping coefficient is normally considered as a constant, obtained from operational experiences in large-scale power systems or from detailed load models in isolated power systems. An industrial isolated power system for aluminum production driven by coal-fired power and large scale wind power is studied in this paper. Since the electrolytic aluminum load is driven by direct current, it is one type of voltage-sensitive load and does not respond to the frequency deviation. This paper proposes a load-damping characteristic control method for such isolated industrial power system with voltage-sensitive load. To decrease the maximum frequency deviation during transient process, a time-varying load-damping coefficient control scheme is presented. Simulation is done on real-time digital simulator (RTDS) and the results verify the effectiveness of the proposed control method.
引用
收藏
页码:1118 / 1128
页数:11
相关论文
共 50 条
  • [1] Sensitivity Analysis of Load-Damping Characteristic in Power System Frequency Regulation
    Huang, Hao
    Li, Fangxing
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2013, 28 (02) : 1324 - 1335
  • [2] Load Flow Analysis with Voltage-Sensitive Loads
    Indulkar, C. S.
    Ramalingam, K.
    [J]. 2008 JOINT INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON) AND IEEE POWER INDIA CONFERENCE, VOLS 1 AND 2, 2008, : 1 - +
  • [3] A Stochastic Economic Dispatch Method Considering a Voltage-Sensitive Load as a Reserve
    Xue, Lin
    Niu, Tao
    Huang, Tianen
    Jin, Hongyang
    Wu, Wenguo
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2022, 205
  • [4] Voltage-Sensitive Load Controllers for Voltage Regulation and Increased Load Factor in Distribution Systems
    Douglass, Philip J.
    Garcia-Valle, Rodrigo
    Ostergaard, Jacob
    Tudora, Octavian Constantin
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2014, 5 (05) : 2394 - 2401
  • [5] Sensitive Load Voltage Compensation with a Suitable Control Method
    Fernandes, Darlan A.
    Costa, Fabiano F.
    Martins, Joao R. S.
    Lock, Alberto S.
    da Silva, Edison R. C.
    Vitorino, Montie A.
    [J]. 2015 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2015, : 1639 - 1644
  • [6] Sensitivity Analysis of Load-Damping, Generator Inertia And Governor Speed Characteristics in Hydraulic Power System Frequency Regulation
    Huang, Hao
    Li, Fangxing
    [J]. 2014 AUSTRALASIAN UNIVERSITIES POWER ENGINEERING CONFERENCE (AUPEC), 2014,
  • [7] Quantifying the Synthetic Inertia and Load-Damping Effect of a Converter-Interfaced Power Source
    Wang, Bin
    Zhang, Yichen
    Sun, Kai
    Tomsovic, Kevin
    [J]. 2018 IEEE INTERNATIONAL ENERGY CONFERENCE (ENERGYCON), 2018,
  • [8] Sensitive Load Voltage Compensation Performed by a Suitable Control Method
    Fernandes, Darlan A.
    Costa, Fabiano F.
    Martins, Joao R. S.
    Lock, Alberto Soto
    da Silva, Edison R. C.
    Vitorino, Montie Alves
    [J]. IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2017, 53 (05) : 4877 - 4885
  • [9] Study on the Characteristic of Sensitive Load under Voltage Sags
    Liu Ronghui
    Pan Aiqiang
    Wang Haibo
    Yang Xiu
    [J]. APPLIED MECHATRONICS AND ANDROID ROBOTICS, 2013, 418 : 269 - +
  • [10] Effect of on-load tap changing transformer control on power-voltage characteristics of compensated EHV transmission line with voltage-sensitive loads
    Ramalingam, K.
    Indulkar, C.S.