摘要
As a kind of potential alternative of traditional mineral insulation oil, mixed oil gives rise to numerous researches on its physicochemical and insulation properties. On this background, a novel three- element mixed insulation oil was developed successfully by our team. Its key parameters meet the requirements of IEC 60296:2012. In order to promote the application of the novel three-element mixed insulation oil in transformers, the research on its insulation characteristics had been carried out under severe non- uniform electric field. In this study, the breakdown voltages and propagation velocities of the novel three-element mixed insulation oil under standard lightning impulse voltage were measured by the rising-voltage method, and the oil gap distance was adjusted from 5mm to 25mm. The dissolved gas characteristics after breakdown fault of the novel three-element mixed insulation oil were also studied at gap distance of 10 mm by gas chromatography. Compared the lightning impulse breakdown voltages of the novel three-element mixed insulation oil with that of mineral oil, the former exhibits much lower breakdown voltages under negative polarity than the latter, and slightly higher under positive polarity. The novel three-element mixed insulation oil also has lower propagation velocities than mineral oil at gap distances from 5 mm to 25 mm. Besides, H-2 and C2H2 are the main gaseous products after lightning breakdown fault of the novel three- element mixed insulation oil. With the increase of breakdown times, the contents of H-2 and C2H2 are obviously increased, which can be used as the characteristic gases of lightning impulse breakdown fault for the novel three-element mixed insulation oil.
引用
收藏
页码:526 / 529
页数:4
相关论文
共 50 条
  • [1] Lightning Impulse Breakdown Improvement Properties of Cellulose Insulation Pressboard Impregnated With Three-Element Mixed Insulation Oil
    Hao, Jian
    Ye, Wenyu
    Li, Hongwei
    Zhang, Hanting
    Zhang, Junyi
    Liao, Ruijin
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2024, 31 (02) : 921 - 928
  • [2] Gas Production Characteristics and AC Breakdown of a New Three-element Mixed Insulation Oil
    Hao, Jian
    Chen, Xin
    Feng, Dawei
    Liu, Xiong
    Wang, Qian
    Gao, Chenyu
    2019 IEEE 20TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2019,
  • [3] AC Breakdown Characteristics of A Novel Three-Element Mixed Insulation Oil for Power Transformer
    Feng, Dawei
    Hao, Jian
    Wang, Qian
    Liu, Xiong
    Liao, Ruijin
    Yang, Lijun
    2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2018,
  • [4] Development Characteristics of Lightning Impulse Discharge Streamer of Three-element Mixed Insulation Oil Based on Simulation Research
    Zhang, Junyi
    Hao, Jian
    Zhang, Jingwen
    Ye, Wenyu
    Qin, Wei
    Liao, Ruijin
    Gaodianya Jishu/High Voltage Engineering, 2024, 50 (12): : 5435 - 5448
  • [5] Study on Moisture Absorption, Power Frequency Breakdown and Gas Production Characteristics of Three-element Mixed Insulation Oil
    Yang T.
    Hao J.
    Chen X.
    Feng D.
    Liu X.
    Liao R.
    Gaodianya Jishu/High Voltage Engineering, 2020, 46 (11): : 4014 - 4022
  • [6] Comparison of AC breakdown characteristics on insulation paper (pressboard) immersed by three-element mixed insulation oil and mineral oil
    Feng, Dawei
    Hao, Jian
    Yang, Lijun
    Liao, Ruijin
    Chen, Xin
    Li, Jian
    HIGH VOLTAGE, 2020, 5 (03) : 298 - 305
  • [7] Microscopic Mechanism of Thermal Cracking and Gas Production Characteristics of Three-element Mixed Insulation Oil
    Xu Q.
    Hao J.
    Ye W.
    Gao C.
    Zhang J.
    Liao R.
    Gaodianya Jishu/High Voltage Engineering, 2023, 49 (03): : 1026 - 1037
  • [8] Creeping Discharge Characteristics of the Liquid/Solid System Composited of Three-element Mixed Insulation Oil and Insulation Pressboard
    Hao J.
    Gao C.
    Chen X.
    Guo P.
    Liao R.
    Li J.
    Hao, Jian (cquhaojian@126.com), 1600, Science Press (47): : 241 - 250
  • [9] Impact of time parameters of lightning impulse on the breakdown characteristics of oil paper insulation
    Sima, Wenxia
    Sun, Potao
    Yang, Ming
    Wu, Jingyu
    Hua, Jiefang
    HIGH VOLTAGE, 2016, 1 (01): : 18 - 24
  • [10] A Novel Three-Element Mixed Insulation Oil and Its Application in 10kV Distribution Transformer
    Hao Jian
    Feng Dawei
    Liao Ruijin
    Liu Xiong
    Chen Xin
    Wang Qian
    Yang Tao
    2019 2ND INTERNATIONAL CONFERENCE ON ELECTRICAL MATERIALS AND POWER EQUIPMENT (ICEMPE 2019), 2019, : 74 - 77