Evaluation of the coefficient of performance of an air source heat pump unit and an air to water heat pump

被引:1
|
作者
Tangwe, S. [1 ]
Kusakana, K. [1 ]
机构
[1] Cent Univ Technol, Fac Engn Built Environm & Informat Technol, Dept Elect Elect & Comp Engn, Free State, South Africa
关键词
vapour compression refrigeration cycle; coefficient of performance; energy optimisation; data acquisition system; SYSTEMS; SIMULATION;
D O I
10.17159/2413-3051/2021/v32i1a7935
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Air source heat pump (ASHP) water heaters are efficient devices for sanitary hot water heating. The coefficient of performance (COP) of the air to water heat pump (AWHP) is constantly lower than that of the corresponding ASHP unit. The study focused on determining the COP of both the ASHP unit and the AWHP. This was achieved by the implementation of both experimental and simulation methods, with the help of a data acquisition system and the REFPROP software. The system comprised of a 1.2 kW split type ASHP unit and a 150 L high pressure geyser. A power meter, flow meters, temperature sensors, pressure sensors, ambient temperature and relative humidity sensor were installed at precise locations on the split type AWHP. Controlled volumes of 150, 50 and 100 L were drawn off from the AWHP during the morning, afternoon and evening for a year. The average COP for the summer and winter, in terms of the input electrical and output thermal energies of the AWHP were 3.02 and 2.30. The COPs of the ASHP unit, in terms of the change in the enthalpies of the refrigerant at the inlet and the outlet of the condenser and the evaporator, were 3.52 and 2.65 respectively. The study showed that the difference between the COP of the ASHP unit and that of the AWHP could be ascribed to the electrical energy consumed by the fan and the water circulation pump during the vapour compression refrigeration cycles. The work provides an energy optimisation opportunity to the manufacturers of this technology, helping to enhance the efficiency and COP of ASHP water heaters.
引用
收藏
页码:27 / 40
页数:14
相关论文
共 50 条
  • [1] STUDY ON PERFORMANCE OF AIR SOURCE HEAT PUMP WATER HEATER
    Duan, Rui
    [J]. PROGRESS IN RENEWABLE AND SUSTAINABLE ENERGY, PTS 1 AND 2, 2013, 608-609 : 987 - 993
  • [2] Using statistical tests to compare the coefficient of performance of air source heat pump water heaters
    Tangwe, S.
    Kusakana, K.
    [J]. JOURNAL OF ENERGY IN SOUTHERN AFRICA, 2022, 33 (01) : 40 - 51
  • [3] Mathematical modelling of the coefficient of performance of a Carnot's Air source heat pump water heater
    Tangwe, Stephen L.
    Simon, Michael
    Meyer, Edson L.
    [J]. PROCEEDINGS OF SAIP2012: THE 57TH ANNUAL CONFERENCE OF THE SOUTH AFRICAN INSTITUTE OF PHYSICS, 2012, : 542 - 549
  • [4] Performance evaluation of a solar energy water heater in conjunction with air source heat pump
    Luo, H. L.
    Peng, J. H.
    Zhong, H.
    Leng, T. T.
    [J]. CRYOGENICS AND REFRIGERATION, PROCEEDINGS, 2008, : 788 - 791
  • [5] Study on performance of air source heat pump water heater/chiller unit under frosting
    Yao, Y
    Jiang, YQ
    Ma, ZL
    Deng, SM
    [J]. ENERGY AND ENVIRONMENT, VOLS 1 AND 2, 2003, : 1563 - 1567
  • [6] Performance evaluation of a compact air-to-air heat pump
    Kent, EF
    [J]. ENERGY CONVERSION AND MANAGEMENT, 1997, 38 (04) : 341 - 345
  • [7] Experiment study on performance of air source heat pump
    Shi, Weixiu
    Pan, Lisheng
    [J]. ENERGY AND POWER TECHNOLOGY, PTS 1 AND 2, 2013, 805-806 : 645 - +
  • [8] Air source heat pump in-situ performance
    Chesser, Michael
    Lyons, Padraig
    O'Reilly, Padraic
    Carroll, Paula
    [J]. ENERGY AND BUILDINGS, 2021, 251
  • [9] Design and Implementation of the Air/Water Heat Pump Controller with Increased Coefficient of Performance
    Tatjewski, Piotr
    Lawrynczuk, Maciej
    Marusak, Piotr
    Rubik, Marian
    Zietek, Piotr
    Szumski, Maciej
    Szumski, Michal
    [J]. 2016 21ST INTERNATIONAL CONFERENCE ON METHODS AND MODELS IN AUTOMATION AND ROBOTICS (MMAR), 2016, : 959 - 964
  • [10] Application Analysis of Air-source Heat Pump Unit
    Shao, Zongyi
    Wang, Yufeng
    Fang, Rui
    [J]. 6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 661 - 664